AGS Parksafe Control Panel Kurulum ve Kullanım Kılavuzu - Sayfa 6
Kontrolör AGS Parksafe Control Panel için çevrimiçi göz atın veya pdf Kurulum ve Kullanım Kılavuzu indirin. AGS Parksafe Control Panel 16 sayfaları. Ventilation control panel
Ayrıca AGS Parksafe Control Panel için: Kurulum ve Kullanım Kılavuzu (16 sayfalar), Kurulum Operasyon ve Bakım (16 sayfalar), Kurulum, Çalıştırma ve Bakım Kılavuzu (20 sayfalar)
Installation & Operation Manual
Board Connections Overview
1. POWER/ LINE IN 110-120Vac mains power should be supplied to the [POWER/LINE IN] connector
using a 3 core cable and fused at 3A. When mains power is supplied to the panel - a red LED
will illuminate located on the front cover.
2. OUTPUT 1 RELAY This relay output switches when any external gas detectors reach 'pre-alarm'
status and the [0-10V OUTPUT] will send 5V to ventilation systems.
OUTPUT 2 RELAY This relay output switches when any external gas detectors reach 'alarm delay'
status and the [0-10V OUTPUT] will send 10V to ventilation systems.
ALARM RELAY This relay output switches when any external gas detectors reach 'alarm delay'
status for longer than the selectable 1-5 minutes time following the [OUTPUT 2] relay.
DAMPER RELAY This relay output can switch together with either OUTPUT 1, OUTPUT 2 or ALARM
relays - selectable in the settings menu.
3. DETECTOR CHAIN 12-24Vdc power and Modbus communication data is wired to Parksafe gas
detectors [DETECTOR CHAIN] - [+ / - / D+ / D-].
Up to 16 detectors can be connected, chained in parallel up to approx. 500 yards from the
panel depending on chain configuration, wire type for power and condition.
Connect detectors in a parallel (daisy chain) method. Any other way may cause
communication issues or damage to the overall system.
For MODBUS communications, a shielded and twisted pair cable is used. The shielding can be
of 2 types: braided [mesh of thin conducting wires] or foil (consisting of a thin sheet of metal
covering the twisted wires).
If you are encountering noise or irregular problems with a Modbus link, the problem is likely
related to grounding, incorrect shielding or wiring mains power next to Modbus wiring.
For more information refer to your Parksafe detector manual.
4. SOUNDER/ STROBE This relay output (24VDC) is for an external sounder alarms/ strobe lighting to
activate on alarm.
5. 24VDC This is a permanent 24Vdc power output for external auxiliary devices.
Max output: 200mA.
6. 0-10V OUTPUT This output can drive ventilation systems. Under normal operating conditions, this
output can send either 0 or 2V – selectable in the settings menu. The [0-10V OUTPUT] will send 5V
when [OUTPUT 1] relay is activated and 10V when [OUTPUT 2] relay is activated.
AGS Parksafe Panel - IOM Iss: 6 10-20
Parksafe
6