Adexa ZBS Series Kullanım Kılavuzu - Sayfa 3

Buz Yapıcı Adexa ZBS Series için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. Adexa ZBS Series 5 sayfaları. Commercial flake ice maker

Features
Computerized control , easy operation & high reliability
Stainless steel exterior
Bell shaped clear ice
Self malfunction analysis
If water shortage or something wrong with the water
supply system,the Ice Maker will restart automatically
in 24hours otherwise you will stop the unit and restart
it again.
PU foamed ice storage cabinet ,so it is insulated
well and it could prevent the ice from melting
High Efficiency , low power consumption
Use fresh water to make clear and healthful ice

Notes before operation

1.The incline angle of the cabinet could
not be over 45° during transportation.
Don't make ice maker upside-down in
case the compressor or refrigerating
system troubles occur.
2.When the i
ce flaker
will be used for the first time or
reused after let it lie idle for a long time,drainage screw
should be unscrewed and a container should be placed under
it to receive wasted water.The first and second ice making
cycles are just for tube system cleaning, the ice made
should not be taken.After the water drained and drainage
screw is screwed, the normal ice making procedures will
begin and you can take the ice.
2
≤45
TROUBLE AND SHOOTING
( for reference of users and technicians )
TROUBLE
CAUSE
1. The voltage is lower
than 187V
Ice f laker does not
2. The ambient
work.
temperature is too low
(lower than 10 )
1. Refrigerant leaks.
2. Refrigerating system
blocks.
3.Solenoid valve opens
Compressor works,
constantly.
but no ice was made.
4.Condensing fan does not
work.
5.Hall element has no
interaction.
1. Water shortage.
2. Ice full.
Compressor does
3. Compressor stops(the
not work.
temperature of shell is
too high).
1. Water shortage in water
The indicator of
supply system.
water shortage lights.
2. Water valve damaged.
3. Tap water pressure too low.
1. There is some ice has not
The indicator of
dropped.
trouble lights.
2. The water tank has not
turned to proper position.
REMEDY
1. Turn off the machine,restart
when the voltage is normal.
2. Try again when the ambient
temperature is over
10℃.
1. Refill the refrigerant and test
leakage.
2. Replace filter for the N
2
filling system.
3. Replace the solenoid valve.
4. Check whether the
condensing for works.
5. Check whether the Hall element
is fine and in proper position.
1. Check the water supply
system (water valve and
water supply tube).
2. Take some ice out.
3. Turn off the machine and
restart 1 hour later.
1. Check and make sure the
water supply system is fine,
then restart.
2. Check the water valve.
3. If it is for tap water, the water
pressure should not be lower
2
than 1Kg/cm .
1. Check whether the solenoid
valve could be open, if not,
replace with a new one.
2. Check whether the switch(SQ1)
could get information from the
rotation of the eccentric wheel.
Check whether the rotating
motor and eccentric wheel skid
around. Check whether the
motor gear is dammaged when
rotate the eccentric wheel by
hand.
7