A unit automatically recovers when the fault condition is removed.
Note :
Please avoid applying a voltage exceeding the rated voltage to an
output terminal. Doing so may cause a power supply to malfunc-
tion or fail. If you cannot avoid doing so, for example, if you need
to operate a motor, etc., please install an external diode on the
output terminal to protect the unit.
1.6 Thermal Protection
¿ KHEA120F/240F/480F, KHNA120F/240F/480F
¡ A thermal protection circuit is built-in.
The thermal protection circuit may be activated under the follow-
ing conditions and shut down the output.
1 W hen a temperature continue to exceed the values determined
by the derating curve.
2 W hen a current exceeding the rated current is applied.
3When convection stops.
4 When peak load is applied in conditions other than those shown
in Section 3.
A unit automatically recovers when the fault condition is removed.
1.7 Output Ripple and Ripple Noise
¡ Output ripple noise may be influenced by measurement environ-
ment, measuring method fig 1.1 is recommended.
+Vout
-Vout
Osiloscope/
Ripple noise meter
Bw:20MHz
C
:Film capacitor 0.1mF
1
C
:Aluminum electrolytic capacitor 22 mF
2
Fig.1.1 Measuring method of Ripple and Ripple Noise
1.8 Remote ON/OFF
¿ KHEA120F/240F/480F, KHNA120F/240F/480F
¡ You can reduce the standby power by Remote ON/OFF.
To do so, connect an external DC power supply and apply a volt-
age to a remote ON/OFF connector.
Table 1.2 Remote ON/OFF Specifications
ON/OFF logic
Between +RC and -RC
L level (0 to 0.5V) or open
Negative
H level (4.5 to 29.5V)
AC-DC Power Supplies DIN Rail Type
C
C
+
1
2
Load
150mm
Differential probe
Output voltage
ON
OFF
June 29, 2020
Instruction Manual
R
*1
Input current
External Power
(20mA max)
Souce
Fig.1.2 Example of use with remote ON/OFF
*1 If the output of an external power supply is within the range of
4.5 - 29.5V, you do not need a current limiting resistor R. If the
output exceeds 29.5V, however, please connect the current limit-
ing resistor R.
To calculate a current limiting resistance value, please use the fol-
lowing equation.
Vcc-(1.1+RiX0.005)
R [W]=
0.005
¡ Please wire carefully. If you wire wrongly, the internal components
of a unit may be damaged.
¡ Remote ON/OFF circuits (+RC and -RC) are isolated from input,
output and PE.
¡ Restart time is 750 ms max .
1.9 Output Voltage Adjustment Range
¡ To increase an output voltage, turn a built-in potentiometer clock-
wise. To decrease the output voltage, turn it counterclockwise.
1.10 Isolation
¡ When you run a Hi-Pot test as receiving inspection, gradually
increase the voltage to start. When you shut down, decrease the
voltage gradually by using a dial. Please avoid a Hi-Pot tester with
a timer because, when the timer is turned ON or OFF, it may gen-
erate a voltage a few times higher than the applied voltage.
¡ When you test a unit for isolation between the output and the
DC_OK, short all terminals of DC_OK.
1.11 Signal Output
Functions of LED indicators and signal output (KHEA series)
¿ KHEA120F/240F/480F, KHNA120F/240F/480F
¡ Functions of LED indicators and signal output in the form of relay
contact are shown below. Checking the presence/absence of volt-
age at the output terminal of a power supply is possible.
Table 1.3 Description of the signal output
Signal Output
DC_OK (LED: Green)
ALARM (LED: Red)
DC_OK (Relay Contact)
*
*DC_OK signal (relay contact) is built in KHEA series. This circuit
is insulated from other circuits (input and output circuits).
Caution on signal outputs :
¡ The timing of signals might be very depending on models, input
and load conditions. Please make sure enough evaluation.
Inside of a Power
SW
Supply
Ri=2040 W
+RC
-RC
Normal
Output is decreasing
ON
OFF
OFF
ON
Short
Open
KH-23