Alish AM5H-A Kullanıcı Kılavuzu - Sayfa 3

Ölçüm Cihazları Alish AM5H-A için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. Alish AM5H-A 5 sayfaları. 5 digital micro-process meter with 2~4 alarms / analog output / rs-485

5 DIGITAL MICRO-PROCESS METER

AM5H-A
with 2~4 ALARMS / ANALOG OUTPUT / RS-485
D
Please understand key indicators & functions at the first operation.
FRONT PANEL & KEY FUNCTIONS
AL1
AL2
AL3
AL4
F
E
Indicators:
Al1: Alarm 1 Indicator
Z: Reset Indicator
Al2: Alarm 2 Indicator
MAX: Max. Holding Indicator
Al3: Alarm 3 Indicator
HD: Value Holding Indicator
Al4: Alarm 4 Indicator
DIO: Communication Indicator
Symbol
Key Name
1. Press this key to enable the reset function & reset indicator (F) is light;
Reset Key
F
press this key again to disable the reset function & reset indicator (F) is dark.
1. In the measuring status, press this key can enter to parameter pages.
Enter Key &
2. In the parameter setting, press this key can save the value & go to
E
Save Key
next parameter.
1. In the measuring status, press this key for 3 sec can enter to alarm
Shift Key &
setting page (The selecting digit will be flashed)
Alarm Setting Key
2. In the parameter setting , press this key can move the cursor left.
Up Key &
1.In the measuring status, press this key for 3 sec can enter to display
value adjustment of "ZERO" & "SPAN"
Display Value
Adjusting Key
2. In the parameter setting, press this key can increase the digits.
1. In the measuring status, press this key for 3 sec can enter to
Down Key &
analog output adjustment.
A/O Adjusting Key
2. In the parameter setting , press this key can decrease the digits.
**1. The following block charts are parameters codes, parameter codes &
parameters will alternate flashing if the parameters can be modified.
2. To modify the parameters, please press
parameter after the modification.
3. Please don't forget the new pass code after modification.
4. In any pages, press
& , or don't press any keys for 2 minutes that will
back to measuring status.
AM5H-A
MANUAL
F
Reset Key/Tare
Z
MAX
E
Enter Key & Save Key
HD
DIO
Shift Key &
Alarm Setting Key
Up Key &
Value Adjusting Key
Down Key &
Analog Output
Adjusting Key
Descriptions
/ /
, and press
to save the
E
P1

GENERAL MODE OPERATING PROCEDURES

Block Charts
Display
Power ON
Measuring Status
Present value for measurement
Alarm 1
Setpoint (AL1)
Alarm 2
Press
E
Setpoint (AL2)
Modify alarm 1 setpoint.
Alarm 3
Press
E
Setpoint (AL3)
Alarm 4
Press
E
Setpoint (AL4)
Press
E
Measuring Status
Present value for measurement.
Display Zero
Modify the zero value.
PS: To use this function to adjust the real zero value.
Adjustment (dZEro)
Press
E
Display Span
Modify the span value.
Adjustment (dSPAn) PS: To use this function to adjust the real span value.
Press
E
Analog Output: "ZERO" &"SPAN" Adjustment
Measuring Status
The following steps are only available for analog output.
A/O Zero
Nodify the A/O zero.
PS: To use this function to adjust the real A/O zero.
Adjustment (AZEro)
Press
E
A/O Span
Nodify the A/O span.
Adjustment (ASPAn) PS: To use this function to adjust the real A/O span.
Press
E
Remark:
1. There are 3 parameter groups of "System Setting Group(SYS)", "Alarm Setting Group(roP)",
"Analog Output Setting Group (AoP)", "RS485 Setting Group(doP)" for modification.
2. Press
to select each group page, and press
for modification or saving the parameters.
3. Some of optional functions of parameter pages still exist, but the functions are disable.

PROGRAMMING MODE OPERATING PROCEDURES

Display
Power On
Measuring Status
Present value for measurement
Press
E
Pass Code
Enter the pass code, or press again if no pass code.
(P.Cod)
Press
E
Pass code is correct that will enter to parameter groups.
P.Code Correct
Pass code is wrong that will back to measuring status.
NO
YES
(SYS)
(roP)
Press
E
Press
E
System Setting Group
Alarm Setting Group
AM5H-A
Descriptions
Alarm Setpoint
Display: "ZERO" & "SPAN" Adjustment
to enter each group or parameter page
E
Descriptions
Parameter Group Setting Procedures
(AoP)
Press
E
Press
E
A/O Setting Group
RS485 Setting Group
P2
Default
Default
(doP)