Fujitsu ABYG 54 Series Kurulum Talimat Sayfası - Sayfa 2

Klima Fujitsu ABYG 54 Series için çevrimiçi göz atın veya pdf Kurulum Talimat Sayfası indirin. Fujitsu ABYG 54 Series 2 sayfaları. Ceiling suspension type split type air conditioner

4. VACUUM
5. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 20 m is charged in the outdoor
(1) Remove the cap, and connect the gauge manifold and the vacuum
unit at the factory.
pump to the charging valve by the service hoses.
When the piping is longer than 20 m, additional charging is necessary.
(2) Vacuum the indoor unit and the connecting pipes until the pressure
For the additional amount, see the table below.
gauge indicates –0.1 MPa (–76 cmHg).
(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum pump
Pipe length
20 m
30 m
40 m
for at least 60 minutes.
Model type
(66 ft)
(99 ft)
(132 ft)
(4) Disconnect the service hoses and fit the cap to the charging valve to
the specified torque.
36,000 BTU/h class
300 g
600 g
(5) Remove the blank caps, and fully open the spindles of the 2-way
(cooling model)
None
(10.6 oz)
(21.2 oz)
and 3-way valves with a hexagon wrench [Torque: 6~7 N·m (60 to
(Reverse cycle model)
70 kgf·cm)].
45,000 BTU/h class
(6) Tighten the blank caps of the 2-way valve and 3-way valve to the
(cooling model)
specified torque.
(Reverse cycle model)
400 g
800 g
None
(14.1 oz)
(28.2 oz)
54,000 BTU/h class
Tightening torque
(cooling model)
6.35 mm (1/4 in.)
20 to 25 N·m (200 to 250 kgf·cm)
(Reverse cycle model)
9.52 mm (3/8 in.)
20 to 25 N·m (200 to 250 kgf·cm)
Blank
12.70 mm (1/2 in.)
25 to 30 N·m (250 to 300 kgf·cm)
cap
CAUTION
15.88 mm (5/8 in.)
30 to 35 N·m (300 to 350 kgf·cm)
19.05 mm (3/4 in.)
35 to 40 N·m (350 to 400 kgf·cm)
1 When moving and installing the air conditioner, do not
mix gas other than the specified refrigerant R410A
Charging port cap
10 to 12 N·m (100 to 120 kgf·cm)
inside the refrigerant cycle.
Connecting pipe
2 When charging the refrigerant R410A, always use
Blank cap
an electronic balance for refrigerant charging (to
measure the refrigerant by weight).
Hexagon wrench
Outdoor unit
Use a 4 mm
3 When charging the refrigerant,
hexagon wrench.
take into account the slight change
3-way valve
Service hose
in the composition of the gas and
with valve core
Charging port
liquid phases, and always charge
from the liquid phase side whose
composition is stable.
Cap
4 Add refrigerant from the charging valve after the
completion of the work.
Gauge manifold
5 The maximum length of piping is 50 m. If the units are
Lo
Hi
further apart than this, correct operation can not be
Vacuum pump
guaranteed.
6. GAS LEAKAGE INSPECTION
CAUTION
1 After connecting the piping, check the all joints for gas
leakage with gas leak detector.
Service hose
2 When inspecting gas leakage, always use the vacuum
pump for pressure. Do not use nitrogen gas.
7. HEAT INSULATION ON THE PIPE JOINTS
CAUTION
(INDOOR SIDE ONLY)
1 Do not purge the air with refrigerants, but use a vacuum
pump to vacuum the installation! There is no extra re-
After checking for gas leaks, insulate by wrapping insulation around the
frigerant in the outdoor unit for air purging!
two parts (Gas and Liquid) of the indoor unit coupling, using the coupler
heat insulation.
2 Use a vacuum pump and gauge manifold and charg-
After installing the coupler heat insulation, wrap both ends with vinyl tape
ing hose for R410A exclusively. Using the same vacuum
so that there is no gap.
for different refrigerants may damage the vacuum pump
Secure both ends of the heat insulation material using nylon fasteners.
or the unit.
And finally fix connection pipe (Liquid) to connection pipe (Gas) by rolling
vinyl tape over coupler heat insulation (Gas) and coupler heat insulation
(Liquid).
7
• Remote control unit settings
REMOTE CONTROL UNIT
(1) Press the START/STOP button and display only the clock.
INSTALLATION
CAUTION
1 Check that the indoor unit correctly receives the
signal from the remote control unit, then install the
remote control unit holder.
2 Select the remote control unit holder selection site by
(2) Press the MASTER CONTROL button continuously for more than five
paying careful attention to the following:
seconds to display the current signal code.
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from
a stove, etc.
1. REMOTE CONTROL UNIT HOLDER INSTALLA-
TION
• • • • • Install the remote control unit holder to a wall or pillar with the tapping
screws.
Remote Control Unit
Remote Control
holder fixing
Unit mounting
(3) Change the signal code with the
1 Set
Remote control
unit holder
2 Push
Tapping
screws
Remote
(small)
control unit
(4) Press the MASTER CONTROL button again to return to the clock
display and change the signal code.
2. SWITCHING REMOTE CONTROL UNIT SIGNAL
CODE
Confirm the setting of the remote control unit signal code and the printed
circuit board setting.
If these are not confirmed, the remote control unit cannot be used to
operate for the air conditioner.
Jumper wire
Remote control unit
signal code
JM2
JM3
Connect
Connect
A (Primary setting)
Connect
Disconnect
B
Disconnect
Connect
C
Disconnect
Disconnect
D
Indoor unit
Printed circuit board
JM1
JM2
JM3
6
Coupler heat insulation (Large)
Connection pipe (Gas)
Indoor unit
Connection pipe (Liquid)
1 Before starting work, check that power is not being
50 m
g/m
Coupler heat insulation (Small)
(164 ft)
(oz/ft)
Nylon fastener (Large)
900 g
30 g/m
2 Match the terminal board numbers and connection
No gap
(31.8 oz)
(1.06 oz/3.3 ft)
Indoor unit
1200 g
Coupler heat
40 g/m
3 Connect the connection cords firmly to the terminal
insulation
(42.3 oz)
(1.41 oz/3.3 ft)
Nylon fastener (Small)
4 Always fasten the outside covering of the connection
Connection pipe (Gas)
Indoor unit
Connection pipe (Liquid)
5 Always connect the ground wire.
Vinyl tape
HOW TO CONNECT WIRING TO THE
• When using an auxiliary pipe, make sure that the fastener used is insu-
lated in the same way.
TERMINALS
CAUTION
A. For solid core wiring (or F-cable)
There should be no gaps between the insulation and the
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
Gas
product.
R410A
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
(3) Using pliers, bend the solid wire to form a loop suitable for the
5
Liquid
POWER
(4) Shape the loop wire properly, place it on the terminal board and
WARNING
B. For strand wiring
1 The rated voltage of this product is 400 V 3ø 50 Hz.
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
2 Before turning on, verify that the voltage is within the
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
342 V to 457 V range.
(3) Using a round terminal fastener or pliers, securely clamp a round
3 Always use a special branch circuit and install a spe-
cial receptacle to supply power to the air conditioner.
(4) Position the round terminal wire, and replace and tighten the
4 Use a special branch circuit breaker and receptacle
matched to the capacity of the air conditioner.
(Install in accordance with standard.)
5 Perform wiring work in accordance with standards
so that the air conditioner can be operated safely and
positively.
6 Install a leakage special branch circuit breaker in
accordance with the related laws and regulations
and electric company standards.
CAUTION
Wire
1 The power source capacity must be the sum of the air
conditioner current and the current of other electrical
appliances. When the current contracted capacity is
insufficient, change the contracted capacity.
2 When the voltage is low and the air conditioner is
difficult to start, contact the power company the
voltage raised.
3 This air conditioner must be connected to a power
source that has an electrical impedance of 0.16 Ω or
less or has a supply current of 100 A or greater. If the
power supply does not meet the specifications,
contact the power company.
8
10
FINISHING
• • • • • Perform test operation and check items 1 and 2 below.
(1) Install the filter guide.
• • • • • For the operation method, refer to the operating manual.
(2) Install the intake grilles.
• • • • • The outdoor unit may not run, depending on the room temperature.
(3) Install side covers A and B (if the unit is installed in a half-concealed
orientation, only install side cover A).
In this case, the 'TEST RUN' signal is received during air conditioner
(4) Install the air filters.
operation (use a metallic object to short the two metal contacts under
the battery compartment lid and send the 'TEST RUN' signal from the
remote control unit).
9
CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating
manual:
(1) Starting and stopping method, operation switching, temperature
adjustment, timer, air flow adjustment, and other remote control unit
operations.
(2) Air filter removal and cleaning.
(3) Give the operating manual and installation instruction sheet to the
customer.
button (
).
• • • • • To end test operation, press the remote control unit START/STOP
button.
(When the air conditioner is run by pressing the remote control unit
TEST RUN button, the OPERATION and TIMER lamps will simulta-
neously flash slowly.)
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do not air flow direction flap and louvers operate normally?
(4) Is the drain normal?
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
ELECTRICAL WIRING
1. CONNECTION DIAGRAMS
Power supply
WARNING
R
Power
S
line
T
N
supplied to the indoor unit and outdoor unit.
1
1
2
2
3
3
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric
parts.
Indoor unit
Outdoor unit
side terminal
side terminal
board. Imperfect installation may cause a fire.
2. CONNECTION CORD PREPARATION
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)
For earth
3. INDOOR UNIT
CAUTION
the insulation to about 25 mm to expose the solid wire.
Use care not to mistake the power supply cord and
connection wires when installing.
board.
terminal screw.
(1) Remove the two tapping screws and pull the control box downward.
tighten securely with the terminal screw using a screwdriver.
Indoor unit
the insulation to about 10 mm to expose the strand wiring.
board.
terminal to each stripped wire end.
Control box
terminal screw using a screwdriver.
Tapping screw
Round
A. Solid wire
B. Strand wire
(2) Remove the Cover A and install the Connection cord.
terminal
(3) Reattach Cover A. Then fasten the control box back into its original
position using the two tapping screws.
Loop
Insulation
Screw with
special washer
Control box
Screw with
Round terminal
special washer
Cover A
Terminal
Round
board
terminal
(4) After wiring is complete, clamp the Connection cord with the Cord
Wire
clamp.
Terminal block
11
TEST RUNNING
AN ERROR DISPLAY
1. INDOOR UNIT
Operation can be checked by lighting and flashing of the display section
OPERATION, TIMER and VERTICAL SWING lamps.
Perform judgment in accordance with the following.
VERTICAL SWING lamp (Orange)
TIMER lamp (Green)
Short the two metal contacts
OPERATION lamp (Red)
under the battery compartment lid.
MANUAL
AUTO
SWING SWING TIMER OPERATION
• Test running
When the air conditioner is run by pressing the remote control unit test
run button, the OPERATION, TIMER and VERTICAL SWING lamps
flash slowly at the same time.
• Error
The OPERATION, TIMER and VERTICAL SWING lamps operate as
follows according to the error contents.
OPERATION
TIMER lamp
SWING lamp
Error contents
lamp (RED)
(GREEN)
(ORANGE)
Indoor EEPROM abnormal
Outdoor EEPROM abnormal
Indoor room temperature sensor
(2 times)
open
Indoor room temperature sensor
(2 times)
shortcircuited
Indoor heat exchanger temperature
(3 times)
sensor open
Indoor heat exchanger temperature
(3 times)
sensor shortcircuited
(4 times)
Float switch operated
(5 times)
Indoor signal abnormal
(5 times)
Outdoor signal abnormal
(6 times)
Indoor fan abnormal
Outdoor power source connection
(2 times)
abnormal
Outdoor heat exchanger
(3 times)
temperature sensor open
Outdoor heat exchanger
(3 times)
temperature sensor shortcircuited
(4 times)
Outdoor temperature sensor open
Outdoor temperature sensor
(4 times)
shortcircuited
Outdoor discharge pipe temperature
(5 times)
sensor or compressor temperature
sensor open
Outdoor discharge pipe temperature
sensor or compressor temperature
(5 times)
sensor shortcircuited
(6 times)
Outdoor high pressure abnormal
Outdoor discharge pipe temperature
(7 times)
or compressor temperature sensor
abnormal
: 0.1s ON/0.1s OFF (flash)
: OFF
: 0.5s ON/0.5s OFF (flash)
(2) Valve cover removal.
(5) Attach the connection cord and cable clips. Make sure that they are
• Remove the one mounting screw.
positioned so that they will not interfere with opening and closing of
• Remove the valve cover by sliding upward.
the intake grille or with removal and installation of the air filters.
Control box
Connection cord
Terminal board
Earth screw
Cord clamp
Connection cord
To outdoor unit
(3) Connect the power supply cord and the connection cord to terminal.
(4) Fasten the power supply cord and connection cord with cord clamp.
Connection cord
Power supply cord
or connection cord
Cable clip
4. OUTDOOR UNIT
CAUTION
When connecting the power supply cord, make sure that
the phase of the power supply matches with the phase of
the terminal board. If the phases do not match, the
compressor will rotate in reverse and will not be able to
compress.
Power supply cord
(1) Service cover removal
• Remove the two mounting screws.
• Remove the service cover by pushing downwards.
Hook
(3 places)
Power supply cord
Direction of the service
cover removal
Service cover
12
2. OUTDOOR UNIT LEDS
Heat & Cool model (reverse cycle) only
When a malfunction occurs in the outdoor
(1) Open up the knockout hole for the fresh-air intake, as shown in the
unit, the LEDs on the circuit board light to in-
LED layout
figure. (If using half-concealed installation, open up the top knockout
dicate the error. Refer to the following table
LED2
LED1
hole instead.)
for the description of each error according to
the LEDs.
For half concealed
installation
LED1
LED2
Error contents
flash
flash
Model abnormal or EEPROM abnormal
1 flash
Lighting
Power source connection error
2 flash
Lighting
Discharge temp. sensor error
3 flash
Lighting
Heat exchanger temp. sensor error
4 flash
Lighting
Outdoor temp. sensor error
5 flash
Lighting
Communication signal error
6 flash
Lighting
Indoor unit error
7 flash
Lighting
Discharge temp. abnormal
1 When removing the cabinet (iron plate), be careful not
8 flash
Lighting
High pressure abnormal
to damage the indoor unit internal parts and surroun-
9 flash
Lighting
Compressor temp. abnormal
ding area (outer case).
10 flash
Lighting
Compressor temp. sensor error
2 When processing the cabinet (iron plate), be careful
Dislighting
No error. Protect operation
not to injure yourself with burrs, etc.
When the fault is cleared, the LED lamp goes off.
(2) Fasten the round flange (optional) to the fresh-air intake, as shown in
However, for discharge pipe temperature abnormal and high pressure
the figure. (If using half-concealed installation, attach to the top.)
abnormal, the LED lamp lights continuously for 24 hours, as long as the
power is not turned off.
[After completing "2 INDOOR UNIT INSTALLATION"...]
(3) Connect the duct to the round flange.
(4) Seal with a band and vinyl tape, etc. so that air does not leak from the
connection.
(5) Power supply cord and connection cord should be fixed with cable
clip as shown in the figure.
Fill in a gap at the entrance of the cords with insulation (seal).
Valve cover
Power supply cord and
connection cord
Hook
(4 places)
Control box
Cable clip
(2 places)
Terminal
Insulation
Cord clamp
(Seal)
Connection cord
(indoor unit and
outdoor unit
connection cord)
CAUTION
Do not make power supply cord and connection cord come
in contact with valve (Gas).
R S T N 1 2 3
Power supply cord
and connection cord
Connection cord
Indoor unit
EARTH
Valve (Gas)
(6) Put the service cover and valve cover back after completion of the
work.
FRESH-AIR INTAKE
Indoor unit
CAUTION
Round duct (option parts)
Duct
PART NO. 9360461094