2VV IC-ModBus Kurulum ve Servis Kılavuzu - Sayfa 11
Kontrolör 2VV IC-ModBus için çevrimiçi göz atın veya pdf Kurulum ve Servis Kılavuzu indirin. 2VV IC-ModBus 13 sayfaları.
7. CONTROL
Code
Name
01
Illegal function
02
Illegal data address
03
Illegal data value
04
Device failure
05
Confirmation
06
Device is busy
08
Memory parity failure
Supported telegrams Modbus, Modbus Module*
Code
Name
03
READ HOLDING REGISTER
04
READ INPUT REGISTER
06
WRITE REGISTER
16
WRITE MULTIPLE REGISTERS
Examples of communication:
Operational data reading:
It is possible to read all operational data of the unit from addresses 15000 to 15008.
Example 1:
Start of the unit, flow rate 60%.
address → value
21000 → 0x01
21001 → 60 (max. flow rate = address 10002)
Turning off the unit:
21000 → 0x00
MODBUS failure codes
Meaning
The requested function is not supported by server
The entered address is out of the range supported by server
The transmitted data is not valid
An unremovable failure occured while executing the request
Code intended for use at programming. The server reports the reception of a valid request but
the execution will take a longer timeu
Code intended for use at programming. The server is busy with executing a long-standing
command
Code intended for use at work with files. Server discovered a parity failure while trying to
read the file
MODBUS failure coder
Meaning
according to Modbus standard
according to Modbus standard
according to Modbus standard
according to Modbus standard
2VV. Creating innovative solutions for you and your business since 1995.
11