7. CONTROL
Address
10007
Modbus Baudrate
10008
Modbus Parity
Service hardware:
Intended for additional functions setup (READ/WRITE)
Address
25000
25001
HeaterCoolDownTime
25002
HeaterCoolDownFlow
LostCommunicattion-
25003
info:
(Status register - READ ONLY)
Address
Name
15000
UnitStatus
15001
Sensor Status
15002
StatusDI1
15003
StatusDI2
15004
AirFlowFanManual
15005
AirFlowFanManualEC
15006
PowerPostheater1
15007
TempEXT1
15008
TempEXT1
Name
Info
0-4800
1-9600
2-19200
3-38400
0-NONE
1-ODD
2-EVEN
Name
Info
Service register - (Factory reset no effect)
Modbus1
Modbus adress port 1
minutes
%
Protect
Info
Status register - read only (Factory reset no effect)
0-OFF
1-ON
2-COOLDOWN
1 - TempEXT1_Error
0 - TempEXT1_OK
1 - DI_open
0 - DI_closed
1 - DI_TACHO_pulzy
0 - DI-TACHO_error
0% = OFF
1%-20% = 1. speed
21% - 40% = 2. speed
41% - 60% = 3. speed
61% - 80% = 4. speed
81% - 100% = 5. speed
0% = OFF
1% - 100% = % PWM
Electric version:
0% = OFF, 1% až 50% = Heat1, 51% až 100% = Heat2
Water version:
0% = OFF, 1 až 100% = Heat1
°C (temp * 10)
°F (temp * 10)
2VV. Creating innovative solutions for you and your business since 1995.
Min. Value
Max. Value
0
0
Min. Value
Max. Value
1
1
Factory_Driver 10003
Factory_Driver 10002
0
Min. Value
0
0
0
0
0
0
0
-400
-400
Default
3
1
2
2
Default
247
1
5
5
20
1
0
Max. Value
Default
2
1
1
1
100
100
100
1000
2120
9