Table 21. Thermal restriction matrix (continued)
TDP (W)
Heat sink type
AMD Milan 24C
180W 2.55-2.65
GHz 128 MB
Table 22. GPU/FPGA thermal restriction matrix
TDP (W)
Heat sink type
Nvidia 500 W
A100 80 GB
GPU
2.5U GPU Heat
Nvidia 400 W
A100 40 GB
GPU
NOTE:
When the 80 GB GPUs are installed, the iDRAC sets the thermal warning threshold to 28° C instead of the normal
38° C.
NOTE:
If System Board Inlet Temp reaches 28° C - 32° C, a warning message is logged. It is possible the GPUs may lower
power consumption to avoid thermal damage. This results in lower GPU performance.
Table 23. Processor and heat sink matrix
Heat sink
2U HPR (Silver) HSK

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any damages to the IT equipment and/or, or both failure from
particulate and gaseous contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and
results in equipment damage or failure, you must rectify the environmental conditions. Remediation of environmental conditions
is the responsibility of the customer.
Table 24. Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
16
Technical specifications
Fan Type
Fan Type
Very High
Performance
sink
Fan
2 x 2.5" SAS + 8 x 2.5" NVMe
ASHRAE A2
Ambient Limit
(Max 35° C)
(Max 30° C)
Not supported
(Max ambient
Not supported
support limit =
28° C)
Supported
Supported
Processor TDP
Supports all TDP
Specifications
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE:
This condition applies to data center environments
only. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or
MERV13 filtration.
NOTE:
Air filtering can also be accomplished by filtering
room air with MERV8 filter per ANSI/ASHRAE Standard
127
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-data
center environments.
Ambient Limit
Ambient Limit
(Max 25° C)
(Max 20° C)
Supported
Supported
Supported
Supported