Environmental
Operating
Storage
Maximum vibration
Operating
Storage
Maximum shock
Operating
Storage
Altitude
Operating
Storage
Airborne Contaminant Level
Class
SC180 Technical Specifications
20% to 80% (noncondensing) with a maximum humidity gradation of 10% per
hour
5% to 100% (noncondensing)
0.21 G at 5–500 Hz for 15 min
1.04 G at 2–200 Hz for 15 min
Half-sine shock 5 G +/- 5% with a pulse duration of 10 ms +/- 10% in
operational orientations only
Z-axis: 30 g 10 ms half sine
X- and Y-axes: 20 g 10 ms half sine
–30.5 to 3000 m (–100 to 10,000 ft)
NOTE: Maximum 35°C up to 2134 m (7000 ft), derate to 30°C for 2134 m
to 3000 m (7000 ft to 10,000 ft).
–300 m to 12,192 m (–1000 ft to 40,000 ft)
G2 or lower as defined by ISA-S71.04-1985