Alpha Communications TekTone CM900 Kurulum ve Kullanım Talimatları Kılavuzu - Sayfa 6
Kontrol Sistemleri Alpha Communications TekTone CM900 için çevrimiçi göz atın veya pdf Kurulum ve Kullanım Talimatları Kılavuzu indirin. Alpha Communications TekTone CM900 8 sayfaları. Emergency call signaling system
Figure 7—Emergency Call Hook-Up Diagram with SF117/2 series
Continuous Duty Door Release, LI381 Corridor Light,
Smoke Detector, and BE007 Corridor Bell
Notes:
1. Use 24 VAC connections on SS106
transformer. To calculate current re-
quirements, add currents of all de-
vices on at the same time. Current
requirements are as follows:
Corridor Lamp with buzzer– .16 amps
Corridor Bell– .2 amps
Door release– .3 amps
Annunciator lamp– .04 amps
2. Wiring must be #18 gauge except
where shown otherwise.
3. BE007 connects to emergency switch
on the same floor only.
4. Door release (if used) must be 24
VDC continuous duty type.
5. Switch current capacity is 3 amps.
6. Power supply maximum current is
1 amp.
7. See Figure 4 for more wiring details.
8. Switches shown in the OFF position.
9. Do not use same transformer for
PK2019/A and PK601A.
Figure 8—Connection Diagram for
Parallel CM800 Panels
Notes:
1. Use 16 VAC connections on SS106
Transformer.
2. Wiring may be #22 except where
shown otherwise.
3. PK2019/A Annunciator Control Unit
may be mounted outside of annun-
ciator enclosure.
TO STATIONS
Page 6 • IL514 CM800/CM900 Emergency Call System Manual
TO ADDITIONAL
EMERGENCY
SWITCHES
SF117/2(B,C)
EMERGENCY
SWITCH
SMOKE
DETECTOR
PK2019/A
BE007
CORRIDOR
BELL
DOOR RELEASE
#22
ANNUNCIATOR
LAMPS
TEST BUTTON
FACTORY
CONNECTED
NOTE: PM110/4N
Panel 1
Tone
R1
Common
Speaker
Normally
R2
Open
Normally
R3
Closed
B
A
Tone
Off
Button
W
Tone
Off
Lamp
S
P
D
N
T1
T2
- # 18
SS106
Transformer
16 VAC
117 VAC
Annunciator
Lamps
Panel 1
PK601A
T1
16 VAC
T2
D
F
117 VAC
PK2019/A
R1
R2
TONE-
TONE
OFF
R3
SPEAKER
LAMP
B
A
W
S
P
D
N
T1
T2
PK612A
C
G
W
E
MODULES ONLY
IL514 General Wiring Figure 6 Rev4 110210 1
Panel 2
PK2019/A
Tone
R1
Common
Speaker
Normally
R2
Open
Normally
R3
Closed
B
Tone
A
Off
Button
W
Tone
Off
Lamp
S
P
D
N
T1
T2
Annunciator
Lamps
Panel 2
IL514 General Wiring Figure 7 Rev1 110210 1
Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.
SS106
TRANSFORMER
(SEE NOTE)
TONE-
OFF
BUTTON
SS106
TRANSFORMER
16 VAC
117 VAC
- # 18
SS106
Transformer
16 VAC
117 VAC