Ayrıca Siemens simatic ET 200MP için: Manuel (24 sayfalar), Manuel (29 sayfalar), Manuel (47 sayfalar), Manuel (26 sayfalar), Manuel (28 sayfalar), Manuel (50 sayfalar), Manuel (34 sayfalar), Kullanıcı Kılavuzu (44 sayfalar), Manuel (30 sayfalar), Manuel (25 sayfalar), Manuel (42 sayfalar), Manuel (28 sayfalar), Manuel (33 sayfalar), Manuel (49 sayfalar), Manuel (36 sayfalar), Manuel (39 sayfalar), Manuel (28 sayfalar), Ekipman Kılavuzu (35 sayfalar), Ekipman Kılavuzu (32 sayfalar), Manuel (29 sayfalar), Manuel (34 sayfalar), Manuel (36 sayfalar), Ekipman Kılavuzu (50 sayfalar), Manuel (45 sayfalar)

Siemens simatic ET 200MP Manuel
Address space for configuration as 4 x 1-channel AQ 4xU/I ST S QI
For the configuration as a 4 x 1-channel module, the channels of the module are divided into
multiple submodules. The submodules can be assigned to different IO controllers when the
module is used in a shared device.
The number of usable IO controllers depends on the interface module used. Observe the
information in the manual for the particular interface module.
Unlike the 1 x 4-channel module configuration, each of the four submodules has a freely
assignable start address.
Figure 4-2
Address space for configuration as 1 x 4-channel AQ 4xU/I ST MSO
For the configuration as a 1 x 4-channel module (module-internal Shared Output, MSO),
channels 0 to 3 of the module are copied to multiple submodules. Channels 0 to 3 are then
available with identical values in various submodules. These submodules can be assigned to
up to four IO controllers when the module is used in a shared device.
● The IO controller to which submodule 1 is assigned has write access to outputs 0 to 3.
● The IO controllers to which submodule 2, 3, or 4 is assigned have read access to outputs
0 to 3.
The number of usable IO controllers depends on the interface module used. Please observe
the information in the manual for the particular interface module.
Analog output module AQ 4xU/I ST (6ES7532-5HD00-0AB0)
Manual, 09/2016, A5E03484696-AD
Address space for configuration as 4 x 1-channel AQ 4xU/I ST S QI with value status
Parameters/address space
4.4 Address space
21