Ayrıca Siemens SINAMICS G120 için: Kullanım Talimatları Kılavuzu (32 sayfalar), Başlarken (30 sayfalar), Donanım Kurulum Talimatları (2 sayfalar), Kurulum Talimatları ve Kullanım Kılavuzu (2 sayfalar), Kurulum Talimatları (2 sayfalar), Kurulum Talimatları (2 sayfalar), Kompakt Kullanım Talimatları (32 sayfalar), Manuel (42 sayfalar), Başlarken (50 sayfalar), Cihaz Kılavuzu (34 sayfalar), Hızlı Kurulum Kılavuzu (2 sayfalar), Uygulama Açıklaması (50 sayfalar), Kompakt Kullanım Talimatları (2 sayfalar), Manuel (31 sayfalar), Uygulama Kılavuzu (34 sayfalar), Kompakt Kullanım Talimatları (2 sayfalar), Kompakt Kullanım Talimatları (2 sayfalar)

Siemens SINAMICS G120 Başlarken

Installing

3.1

Installing the Power Module

Danger of death caused by high leakage currents when the external protective conductor is
interrupted
The inverter conducts high leakage currents > 3.5 mA via the protective conductor. When
the protective conductor is interrupted, touching live components can result in electric
shock, which can lead to death or serious injuries.
• Connect a protective conductor, which satisfies at least one of the following conditions,
Converters with CU250S-2 Control Units
Getting Started, 10/2013, FW V4.6, A5E32899990B AA
WARNING
to the inverter:
– The protective conductor is routed so that it is protected against mechanical damage.
Cables routed in control cabinets or enclosed machine enclosures are considered to
be adequately protected.
– The protective conductor routed as an individual conductor has a cross-section of
≥ 10 mm² Cu.
– In a multi-core cable the protective conductor has a cross-section of ≥ 2.5 mm² Cu.
– Two parallel protective conductors with the same cross-section are installed.
– The protective conductor corresponds to the local regulations for equipment with
increased leakage current.
Installing
3