Actulux SVM EI 24V-8A Kurulum Talimatı - Sayfa 4

Kontrol Paneli Actulux SVM EI 24V-8A için çevrimiçi göz atın veya pdf Kurulum Talimatı indirin. Actulux SVM EI 24V-8A 13 sayfaları. Control panel for fire ventilation

Actulux SVM EI 24V-8A Kurulum Talimatı
+
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
-
+
-
Connection to motor- (actuator-) output and line monitoring
The actuators (motors) must be connected to the actuator output on the output terminals 2-3.
It is possible to connect and disconnect the line monitoring on the actuator output (the factory setting is
"connected"). The cables to the actuators can be connected in series or parallel or a combination of these
(please see drawing with examples or connection diagram on the mid pages).
It is important to keep the right polarity of the cables - The actuators must always be connected through a
current limiter, e.g. the Actulux LIP or similar.
Cable monitoring (line monitoring) on the motor output
The control is equipped with 3 possible settings for cable
monitoring (line monitoring), which can be configured by
means of jumper J2.
Jumper J2 mounted in pos. »Motor line«
Line monitoring between terminal 2-3.
Jumper J3 (actuator output) is set according to
the number of termination resistors (27 KΩ) to
be detected – 1 to max. 4 lines can be detected
by moving jumper J3 – this means that the cable
installation between the control panel and the
actuators can be established in series connection
(cable connection from e.g. skylight 1, further
to skylight 2, etc.), or parallel connection (cable
connection from each skylight to the control), or
a combination of these. However, as mentioned
max. 4 different lines can be detected each
terminated with a 27 KΩ resistor.
For SVM EI 24V-5A:
the max. allowed current is 5A.
For SVM EI 24V-8A:
the max. allowed current is 8A.
Jumper description
Number of connected 27Kohm terminal
J3
resistors for actuator output
J2
Chooses line monitoring through motor
terminals 2-3 (Mot Mon) or separate
wire terminals 1-3 (Ext Li Mon), or no
line monitoring when J2/J3 is removed
Fuse 8A for actuator output
F1
24V
Red 2,5mm2
Black 2,5mm2
- 24VDC +
Max. 8A
FUSE F1 - fast
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
J2
4
J3
3
2
1
Max. Torque 0.5 Nm
1
2
PE
L1
N 1
Line 1
Actuator
24V Out
1 Cannel LIP 7
1
2
Blue
2
1
5
M1
Blue
Blue
5
7
6
Brown
2
1
M1
M2
Next LIP
6
8
Brown
Brown
3
4
2 channel LIP 6
Next LIP
6
J1
RESET
YEL
YEL
YEL
AC FAIL
LINE FAIL
BATT LOW
Jumper J2 in pos. »Ext 3 wire«.
Line monitoring between terminal 1-3:
NTC
With jumper J3 (actuator output) it is chosen, how many lines (number of 27 KΩ)
you wish to detect - the same way as the motor line.
J9
Keyboard
This setting demands 3 wire cable from motor output to motor.
Without keyboard jumper mounted
No line monitoring
To disable line monitoring, place the 27KΩ resistor in terminal 1 and 3.
Set J2 to "Ext 3 wire monitor (line 1)", and set J3 to "1".
BLUE
Now use Actuator out on 2 and 3.
DOME OPEN
NOTE: it is recommended that line monitoring should always be activated wherever
possible
LED 4 indicates if there is any fail on the actuator output. Steady light if wire is broken.
"Flashing fast" in case output is connected to earth. Flashing slow if output is shorted.
NOTE: When Flashing RESET or close is not possible
Max. Torque 0.5 Nm
Current limiter type LIP function and setting (if mounted)
4
5
6
7
8
9
10
11
12
13
14
15
3
The current limiter type LIP (mounted on the opening system) is used as current limiter between the
Alarm Out
Failure Out
Manuel Control Point
24V/48VDC supply and 1 or 2 actuators. When the adjusted current limit is reached, the speed of the
actuators is reduced. When the max. power on the actuator is exceeded, the actuator stops. On the
24V /48V types (LIP5, LIP6 or LIP7) max. 3 times overload cut outs in the same direction is allowed.
After that it will not be possible to run in this direction again, before the motor has run in the opposite
direction. This in order to protect the actuator gear mechanism.
1
2
3
4
6
7
2,2KΩ
Please note that when opening, the red LED in the LIP must light. This indicates that polarity to
10 KΩ
J1
Fire switch BVT No. 1
actuator is correct.
1
2 3
4
6
7
2 3
Table of LIP settings
1
4
6
7
2,2KΩ
10 KΩ
Opening System
3A/1.5A SA Power
J1
24V/48V
Fire switch type BVT.
Single, Double, Large
Fit J1 in last BVT for
line monitoring
Extra relay print #111933
DIP 1
ON
provides 2 additional
DIP 2
OFF
potential free contacts
each 30V 0,5A
Type
Board
Board
Voltage and
no.
descrip.
function
LIP5
121315 A043
24/48V
1 channel
LIP6 *
121330 A044
24/48V
2 channels
LIP7
121305 LIP7
24/48V
Basic
1 channel
LIP7
121306 LIP7
24/48V 1 channel
TA
Tandem
LIP7***
121308 LIP7
24/48V
OC
1 channel Syncro
m/position ind.
* SA Power Large - parallel operation: Jumper OPT mounted - both motors stop at the same time if one stops because of overload.
** When DIP4 is OFF = Tandem mode - both motors stop at the same time if no current flows in one. (1.5 sec. reaction time)
*** Requires actuator with Reed. (3-core incl. black cable)
**** OFF = No delay between Master og Slave / ON = Seven sec. delay between Master and Slave.
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
12
LOCKOUT
11
BUS FIRE
10
BUS COMFORT
9
SPRINKLER
8
OPTION
7
WEEK OPEN
6
FAIL RELAY M.
Set J11 for batteri backup
of terminal 23
5
SNITCH
4
SERVICE TIMER
J11
3
TEMP DETECT
2
FAIL SAFE
1
Con. Fire. Sig
DIP settings see page 13
END termination
J7
®
BUS Slave
J6
®
START termination
®
J4
®
BUS Master
J5
Connection from
prev. unit.
16
17
18
19
20
21
22
23
24
25
26
27
Smoke
Comfort
Weather
Prior
L1 In
L2
No.1
Down
L1 O ut
Up
24V
AC/DC
L1 In
L2
4A/2A SA Power
2.5A/1.25A SA Power
Nr.2-20
Single, Double, Large
Mini
L1 O ut
OFF
ON
ON
ON
(only last sensor)
DIP
DIP
DIP
DIP
DIP
1
2
3
4
5
27K
ON
OFF ON** 27K ON
See
27K
diagram
ON
above
27K
ON =
OFF = Slave
ON
Com
ON = Master
27K
ON =
OFF = Slave
ON
Com
ON = Master
7
Actuator
J2
Motor line monitor
Ext 3 wire monitor (line 1)
4
J3
3
2
1
1
2
3
Line 1
+
-
Actuator
24V Out
+ +
27K Ohm
(Only last
actuator)
#111980
Firemans Priority switch
CLOSE
OPEN
R
E
S
E
T
1
6
AWR-24
2.5A/1.25A Rotary 100
LIP5/6
2A/1A SA Power Mini
LIP7
OFF
#111960
#111961
OFF
DIP
DIP
DIP
6
7
8
Not mounted
M1-M2 delay =ON
Not mounted
OFF = Syncro Mode
Not in
ON = Tandem Mode ****
use
OFF = Syncro Mode
Not in
ON = Tandem Mode ****
use