DIGM Technology GSM-0308WPC Kullanıcı Kılavuzu - Sayfa 8

Kontrolör DIGM Technology GSM-0308WPC için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. DIGM Technology GSM-0308WPC 9 sayfaları. Gsm water pump controller and monitoring system

GSM-0308WPC User Manual
 
1.5 
Delete Administrator Number in the list: 
*103*A# 
Deleting administrator tel. no. on the list 
A = administrator no. (1 – 5) 
Example: Send *103*5#, the system will delete the Admin 5 
 
Enquiry Signal Strength: 
1.6 
*104# 
Check signal strength on the GSM connection 
Enquiry for Signal Strength 
CSQ = 0 – 10 (Weak Signal) 
CSQ = 11‐ 20 (Average Signal) 
CSQ = 21 – 30 (Good Signal) 
CSQ = Above 30 (Excellent Signal) 
1.7 
Time Schedule to send SMS Reminder to the Administrator 
*109*XXX# 
SMS check message to say the unit is still up and running. 
XXX = Days (Value = 000 ‐ 255, must be in 3 digits, every week = 007) 
Default as 000 (Not Sending SMS reminder) 
Default Text reads as    "Hi! I'm OK"   (Can edit the text using *111* Command)  
Example:  (send)   *109*002#     the system will start to calculate from the moment it receives 
the SMS. After 2 days, it will send out a SMS reminder. 
Note: If the system had been restarted, it will clear the time to ZERO and recalculate again for 
2 days from the moment the system restarted, then send out the SMS reminder after 2 days. 
 
 
 
 
 
 
8 | P a g e