HSPC terminal connectors are inserted in the module and the module is installed.
The CoriolisMaster is wired for power. Refer to the CoriolisMaster Operating Instructions for
details (See
Additional information
To apply power:
1.
Connect the HSPC module to the flow computer or remote controller TFIO or I2C Bus interface.
2.
Apply power (input voltage) to the flow computer or remote controller.
3.
If the HSPC module is connected to an external supply, switch on the power.
4.
Verify that the HSPC module LED indicators show the module is powered.
5.
Apply power to the CoriolisMaster.
6

Configure the HSPC input

This procedure enables and configures the HSPC Module from the I/O Interface on PCCU.
Prerequisites:
The HSPC module has been installed and powered.
PCCU 7.76 or later must be installed in the laptop/PC used to connect to the flow computer or
controller.
The HSPC has been successfully detected by PCCU.
To configure the HSPC module:
1.
Start PCCU.
2.
Connect to the flow computer or remote controller with PCCU on Entry Mode.
On the PCCU navigation tree, expand I/O Interface (I/O System on the RMC) and then
3.
select TFIO Modules (TFIO-A Modules or TFIO-B Modules on the RMC).
4.
Select the TFIO Module State tab.
5.
Verify that the HSPC module is detected. The module should display under the configured
address, and it displays as: Available. This indicates that the flow computer or controller has
detected the TFIO module in its communication bus, but the module is not yet ready for use.
6.
Click on the module address field and select Online from the drop-down list.
Click Send. The State of the TFIO module displays: Online
7.
detected module has an address of 00 (default). The module state displays under that address.
The navigation tree updates the ONLINE modules.
Figure 6-1: TFIO Module State: HSPC module online
8.
Expand ONLINE on the PCCU navigation tree. The list of all online modes displays. In this
example, only one module is displayed and is identified by type and address: TFIO 8/HSPC
I:00. Note that the address label on the module plate uses single digits (0-7). The interface
uses 2 digits (00-07).
Select TFIO 8/HSPC I:00. The Digital I/Os tab for the HSPC module displays. Remain on
9.
this tab.
10. Configure the wired HSPC module point as a Digital Input (DI):
a. Locate the I/O point. In this example, Digital I/O 1 identifies the module's J1-1 and J1-2
points
(Figure
b. Click the Type field next to the point used for connection.
c.
Select: DI-Power Saving (2.3 MA) from the drop-down list.
11. Leave the default Debounce setting: OFF.
for a link to the document).
6-2).
(Figure
21 08 74 4MN A A | HS P C C ON FIG UR AT IO N G UI DE | 7
6-1). In this example, the