aerauliqa CTRL-XWS Kullanım Kılavuzu - Sayfa 19

Kontrolör aerauliqa CTRL-XWS için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. aerauliqa CTRL-XWS 20 sayfaları.

aerauliqa CTRL-XWS Kullanım Kılavuzu
5.2.7 SETTING OF THE CONSTANT DATA
+
Press contemporaneously
Four lines are shown on the display and then the message CONF. is displayed.
Press
to scroll the setting menu.
Parameters:
P.r.o.b.
Cor.1. = ceiling temperature probe correction
Cor.2. = ground temperature probe correction
SCAL = °C/°F Celsius or Fahrenheit degree
Air
SP.Lo = % of minimum speed
SP.Hi = % of the maximum speed
P.b.Su. = proportional band of regulation in summer mode
P.b.Vi. = proportional band of regulation in winter mode (destratification)
t.Lo.A = minimum temperature alarm value
t.Hi.A = maximum temperature alarm value
d.SE.t = temperature alarm relays hysteresis
t.on.v.= on time (active) for ventilation timing (t.on=0 constant ventilation)
T.of.v.= off time (pause) for ventilation timing (t.off=0 constant ventilation)
t.Int.= 0-10V integration time
Star = % minimum starting speed
5.3 MEMORY OF THE REGISTERED TEMPERATURE (the values are retained even with the controller switched off)
+
Press
: the diagram is displayed followed by the maximum registered temperature value. Keeping
CLEA. is shown and the memory is cleared.
-
Press
: the diagram is displayed followed by the minimum registered temperature value. Keeping
CLEA. is shown and the memory is cleared.
5.4 SYSTEM RESET
Disconnect the controller from the main power supply.
Connect the controller to the main power supply and keep
+
Release
and wait for the reset.
Attention: Any setting will return to the default.
-
and
for about 5 seconds.
+
pressed until the word BOOT is displayed.
19
+
pressed for more than 3 seconds, the word
-
pressed for more than 3 seconds, the word