esera automation 11220 Kullanıcı Kılavuzu - Sayfa 5

Anahtar esera automation 11220 için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. esera automation 11220 7 sayfaları. 8-fold switch module with pushbutton inputs for 1-wire bus

esera automation 11220 Kullanıcı Kılavuzu
Art. No. 11220
10
Software / Control
The 1-Wire interface of the 8-fold digital output 8/8 is controlled by standard commands for the DS2408 module.
The outputs switched via the pushbutton interface or manual operation can be controlled via the
1-Wire interface can be read back.
11
Control by 1-Wire Controller / 1-Wire Gateway
The 1-Wire interface of the 8-fold digital output 8/8 is controlled by standard commands for the DS2408 device.
The outputs switched via the pushbutton interface or the manual mode can be read back via the 1-Wire interface.
The 8-fold switching module can be controlled very easily via a 1-Wire controller / 1-Wire gateway. Two
commands are available for this purpose. Below are the two commands.
11.1
Switching an output relay
To switch a relay output, use the following command, which only sets the selected output to 0 or 1.
Command: SET,OWD,OUT,OWD-Number,Output,Value
Example: set,owd,out,2,1,1 => OWD Number 2, output 2 will be switched to "on".
After switching the output latest status will be output as confirmation.
11.2
Switching of all output relays (Port)
There are applications and modules where it is necessary to switch all outputs with one command.
With one command, all outputs of the 1-Wire module are set to a specific state, which means that the previous
output state is overwritten.
The 1-Wire Controller / the 1-Wire Gateway takes over the command adaptation to the connected
Module 8-fold switching module.
The output value is output as decimal value 0-254. Each relay output has a valence which is summed up.
Output 1 = 1, Output 2 = 2, Output 3 = 4, Output 4 = 8, Output 5 = 16, Output 6 = 32,
Output 7 = 64, Output 8 = 128.
For example, if you want to switch Output 1, 3 and 5 to 1, add the output value together.
Here e.g. 1 + 4 + 16 = 21
All other relay outputs are switched to 0. If all outputs are to be switched to 0 or off, the output value is 0.
Permissible output values for 1-Wire digital outputs: 0 - 255
Command: SET,OWD,OUTH,OWD-Number, value
Example: set,owd,outh,2,15 => OWD Number 2, outputs 1 to 4 will be switched to "on".
After switching the output, latest status will be output as confirmation.
11.3
Data Output 1-Wire Controller / 1-Wire Gateway
For the 8-fold digital output 8/8, the following data is output for the binary / digital inputs (button interface) and
relay outputs.
The input and output values are output as decimal value 0-254 and in a second data set binary with 0 and 1.
Each input and output has a valence, which is added up in each case.
Input pushbutton interface:
Input 1 = 1, Input 2 = 2, Input 3 = 4, Input 4 = 8, Input 5 = 16, Input 6 = 32, Input 7 = 64,
Input 8 = 128.
Relay Output:
Output 1 = 1, Output 2 = 2, Output 3 = 4, Output 4 = 8, Output 5 = 16, Output 6 = 32, Output 7 = 64,
Output 8 = 128.