Artistic License Dali-Scope Kullanıcı Kılavuzu - Sayfa 5

Ölçüm Cihazları Artistic License Dali-Scope için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. Artistic License Dali-Scope 8 sayfaları.

If new devices are added to an existing
network, short addresses already in use will
be avoided.
The commissioning process is separate to the
configuration of the devices and only needs
to be done once.
Dali-Scope Operation
Dali-Scope has six menu options:
y READ - Read incoming DALI commands
y TEST - Transmit DALI levels
y STATUS - Displays properties of a fixture
y ADDRESS- Shows & configures current
channel/group assignment
y CONFIG - Changes configurable
properties of a fixture
y ADVANCED CONFIG - Dali-Scope
setup options
Power
Power is provided by two AA batteries.
Approximate battery life is 12 hours continuous
and 6 months on standby. Dali-Scope can be
powered using rechargeable batteries.
Dali-Scope features an automatic power off
timer to conserve battery life. This may be
configured in the ADVANCED CONFIG menu.
Switch on by pressing the
off, hold the
key for 5 seconds.
During power on, Dali-Scope automatically
searches for DALI devices. This search will
only include devices that have been given
a channel number / short address. To find
devices that are unconfigured, please refer
to the ADDRESS section.
Important: Dali-Scope will not provide power
onto the Data Bus. Please ensure a DALI Bus
PSU is present such as a Rail-PSU-D4.
Note: Only one controller should be present
on the DALI circuit at any time. When using
the READ menu options, Dali-Scope does not
transmit data messages so can be added to
the DALI circuit at the same time as a DALI
controller.
Dali-Scope User Guide
READ
There are 3 options available:
y CURRENT VALUE: Displays the value of
y LATEST VALUE: Displays the latest
(The two options above display all the
information received. This will include control
commands).
y DISPLAY STATS: Displays the number of
(Note: The counter resets to 0 when it reaches
256).
TEST
Use the TEST button to scroll through the
different sub menus below:
y RIG: [CHANNEL / GROUP / SCENE] –
key. To switch
y WALK: [CHANNEL / GROUP / SCENE] –
y ALL: [BROADCAST] – All devices at a
the command or level that is transmitted by
the controller. This value will then be held
until the READ button is pressed again.
values that are transmitted on the circuit.
The screen will refresh each time a new
value is received.
commands being sent (Tx) and received
(Rx) on a DALI circuit.
Sends a single value
- UP or DOWN used to control the value
(0-100%)
- LEFT or RIGHT used to select the channel
/ group / scene index
- LEFT (hold) then RIGHT used to select
between channel / group / scene
Walks between start and end index
- UP or DOWN used to select start index
- LEFT or RIGHT used to select end index
- LEFT (hold) then RIGHT used to select
between channel / group / scene
specific level
- UP or DOWN used to select level (0 –
100%)
Page 5