Installation and Operating Manual
Wind relay SIWR
General information
Wind relay SIWR is used with wind sensor SIWS in conjunction with the components
of the SI and Dupline building management system, predominately to protect elec-
tric motor-operated blinds, shades, skylights, etc.
Functionality and output functions
The reed contacts in the SIWS are arranged in such a way that the constant current
generated in the SIWR is pulsed. The frequency of the pulsating current is thus pro-
portional to the prevailing wind force. The arrangement also detects wire breaks or
increased transition resistances and signals these by an alarm, if necessary the A1
output will be energized. A short circuit cannot be detected, but also will not result in
the destruction of the input.
Two LEDs on the front of the evaluation unit show the current status of the device. If
the "fault" LED flashes, the monitoring function is still working but the cause of the
fault must still be determined. If a fault occurs that affects proper monitoring, the
"fault" LED lights up constantly (no flashing) and the output contact is switched on,
indicated by the "on" LED.
Faults
Fault indicator
"Fault" LED flashes, output A2 (1.6)
flashes, "on" LED does not light up,
constant output A1 (1.2) 0 V, relay
not actuated, monitoring function
continues to work
"Fault" LED lights up, A2 (1.6) 24 V,
"on" LED lights up, A1 (1.2) 24 V, relay
actuated
The fault indicator automatically resets within approx. 10 s of the fault being correct-
ed, or it can be manually reset by briefly disconnecting the supply voltage. The de-
sired switch value is set via an 8-level switch on the front of the device. When setting
the value, ensure that a higher wind threshold is first accepted due to safety reasons
after briefly disconnecting the supply voltage. A lower wind threshold is immediately
accepted. The semiconductor outputs are designed for use in the SI system. The relay
output facilitates use outside of the system as well.
Mounting
Installation may only be carried out by an authorized, trained technician. Snap onto
mounting rail. Immediately after switching on the supply voltage, the "fault" LED will
flash briefly to signal the initialisation phase.
Guarantee
All professionally installed, unaltered devices are covered by warranty during the
statutory guarantee period from the day of purchase by the end user. The guaran-
tee is not applicable to damage incurred during transport or caused by short-circuit,
overloading or improper use. In the event of defects in workmanship or material,
which are discovered within the guarantee period, the company will provide a repair
or replacement free of charge. The guarantee will be rendered null and void if the
device is opened without authorization.
Please note the following information: The guarantee covers only the proper func-
tion of the device, not the entire system. No liability is accepted if wind damage
occurs to the external system, as the protective capability of the SIWR depends on
many external factors, such as:
» where the anemometer is installed,
» the effects of wind velocity on buildings, for example,
» whether the wind capacity of the external system was correctly estimated,
» the response time/ease of movement of the motors and external system and
» proper installation.
Technical Data
SIWR
Oper-
B1
ating
B2
voltage
Internal
c onsumption
Adjustment ranges
wind force 3–10 (see wind force table below)
switch-on delay max. 1 s, switch-off approx. 10 min.
Switching hysteresis
after wind force drops to next lowest level
Indicators
3931152 | 11/2013 | Doepke Schaltgeräte GmbH, Stellmacherstraße 11, D-26506 Norden
Possible cause
» Line resistance too high
» High contact resistance at reed
contact
» Poor terminal positions
» Wire breakage in anemometer
» Fault in anemometer
» Anemometer not connected
0 V DC
24 V DC + 10 %
approx. 10 mA
"on" LED: threshold exceeded
"fault" LED: SIWS faulty, wire breakage
SIWR
A1
max. +24 V / 50 mA if wind threshold is exceeded
Outputs
A2
Relay output
potential-free relay output, changeover contact 230 V / 2 A
15
16
18
Protection class
IP 40 (after installation in distribution board)
Housing
Terminals
Max. clamping area
Wire diameter
Mounting
distribution board housing for mounting on DIN rail
Ambient t emperature
Design requirement
Wind force table
Wind
Description
force
0
calm
smoke does not ascend immediately,
1
light air
2
light breeze
3
gentle breeze
moderate
4
breeze
paper is blown around on the ground
5
fresh breeze
larger branches move, waves form on water
sturdy branches move, wind can be heard
6
strong wind
at corners of the building, white caps
weaker trees move, shouting is hindered
7
high wind
8
gale
roof tiles etc. and lightweight structures
9
strong gale
trees and lightweight structures are
10
storm
11
violent storm
12
hurricane
1)
The underlined values are the adjustable switch values.
Wiring
18
15
1.1
1.5
A1
A2
1.2
1.6
EIN
STÖRUNG
externe Anzeige
(external display)
3
10
4
9
8
6
7
SIWR
B1
B2
1.4
1.8
constant semiconductor output
flashing semiconductor output
max. +24 V / 50 mA if fault occurs
normally opened contact
normally closed contact
common pole
Cycoloy® (ABS)
U-clamp terminal
1 × 2.5 mm² (solid)
1 × 1.5 mm² (stranded)
min. 0.4 mm
-10 °C to +45 °C
DIN EN 60669
Conditions
completely still (no wind)
leaves still motionless
just perceivable
leaves move,
water ripples
small branches move,
on waves
by the wind
whole trees move
are blown around
blown around
heavy damages
destructive effects
2.1
1.1
16
1.5
2.1
S1
S2
2.2
2.6
Windstärke
5
m/s
1)
0–0.2
0.3–1.5
1.6–3.3
3.4–5.4
5.5–7.9
8.0–10.7
10.8–13.8
13.9–17.1
17.2–20.7
20.8–24.4
24.5–28.4
28.5–32.6
32.7–36.9
SIWS
24 V DC
0 V DC