Control Input X1, X2
With BL 9228 soft start begins by pressing the start button. By pressing
the stop button braking will start.
Adjustment Facilities
Potentiometer
Description
M
Starting voltage
on
t
Ramp-up time
on
I
Braking current
Br
Set-up Procedure
Soft start:
1. Press start button. Turn potentiometer "M
to turn without excessive humming.
2. Adjust potentiometer "t
" to give desired ramp time.
on
3. On correct setting the motor should accelerate up to nominal speed.
If the start takes too long fuses may blow, especially on motors with
high inertia.
Attention:
If the ramp-up time is adjusted to short, the internal
bridging contact closes before the motor is on full speed.
This may damage the bridging contactor or bridging
relay.
Connection Examples
L1
L2
L3
N
S
Q1
I> I> I>
1
3
5
K1
2
4
6
L1 L2 L3
A1
A2
BL9228/010
T1
T2
T3
P1
P2
P3
U
V
W
M
3~
T1
T2
T3
P2
P3
U
V
W
M 3~
T1 T2 T3
P1 P2 P3
U
V
W
M 3~
Auxiliary voltage U
= AC 400 V or AC 230 V
H
Initial setting
fully anti-clockwise
fully clockwise
fully anti-clockwise
" up until the motor starts
on
X1
X2
13
43
33
14
24
44
34
without
temperature
monitoring
K1
M5668_b
temperature
monitoring by
bimetallic contact
temperature
monitoring by
PTC-sensor
Set-up Procedure
Braking:
Press stop button and adjust with potentiometer "I
the desired value. Please adjust the braking current high enough so that
the brake time is shorter than 10 sec. The brake current should be limited to
1.8 ... 2 x I
of the motor. If the brake function at 1.8 ... 2 times of rated
N
current has not finshed within 10 sec the load is too high. The next larger
motor shoud be used. To avoid an overload of the device and the motor,
the brake current should be measured with a moving coil instrument in the
motor connecting line T1.
Temperature monitoring:
BI 9028 features overtemperature monitoring of its internal power
semiconductors. The unit is therefore protected against overheating during
the set up procedure. BI 9028 can be reset after the semiconductors have
cooled down by momentarily removing the auxiliary supply voltage.
Safety Notes
-
Never clear a fault when the device is switched on.
-
The user must ensure that the device and the necessary
components are mounted and connected according to the locally
applicable regulations and technical standards.
-
Adjustments may only be carried out by qualified specialist staff and
the applicable safety rules must be observed.
L1
L2
L3
S
Q1
I> I> I>
1
3
5
K1
2
4
6
L1 L2 L3
A1
A2
BL9228/010
T1
T2
T3
P1
P2
P3
U
V
W
M
3~
T1
T2
T3
P2
P3
U
V
W
M 3~
T1 T2 T3
P1 P2 P3
U
V
W
M 3~
Auxiliary voltage U
= DC 24 V
H
4
" the braking current to
Br
X1
X2
13
43
33
14
24
44
34
without
temperature
monitoring
K1
M9766_b
temperature
monitoring by
bimetallic contact
temperature
monitoring by
PTC-sensor
11.01.21 en / 335A
DC 24V
0V
control voltage