DOLD VARIMETER IMD RL 5898 Orijinal Talimatların Çevirisi - Sayfa 7
Endüstriyel Ekipmanlar DOLD VARIMETER IMD RL 5898 için çevrimiçi göz atın veya pdf Orijinal Talimatların Çevirisi indirin. DOLD VARIMETER IMD RL 5898 17 sayfaları. Insulation monitor
Ayrıca DOLD VARIMETER IMD RL 5898 için: Orijinal Talimatların Çevirisi (8 sayfalar), İzleme Tekniği (12 sayfalar), İzleme Tekniği (12 sayfalar)
Technical Data
Clearance and creepage
distances
Rated insulation voltage:
Overvoltage category:
Rated impuls voltage /
pollution degree:
Measuring circuit L(+)/L(-) to
auxiliary voltage A1(+)/A2 and
indicator relay contacts K1, K2: 4 kV / 2
Auxiliary voltage A1(+)/A2 to
indicator relay contacts K1, K2: 4 kV / 2
Indicator relay contact K1 to
indicator relay contacts K2:
Bus A, B to
measuring circuit L(+)/L(-) and
auxiliary voltage A1(+)/A2 and
indicator relay contacts K1, K2: 6 kV / 2
Insulation test voltage
Routine test:
EMC
Electrostatic discharge (ESD): 8 kV (air)
HF irradiation:
80 MHz ... 1 GHz:
1 GHz ... 2.7 GHz:
Fast transients:
Surge voltage
Between
wires for power supply:
Between wire and ground:
HF-wire guided:
Interference suppression:
Degree of protection
Housing:
Terminals:
Housing:
Vibration resistance:
Shock resistance:
Climate resistance:
Terminal designation:
Wire connection
Cross section:
Stripping length:
Wire fixing:
Wire connection Bus
pluggable cage-clamp terminal: 0,14 ... 0,5 mm
Insulation of wires or
sleeve length:
Fixing torque:
Mounting:
Mounting position:
Weight:
Dimensions
Width x height x depth:
Classification to DIN EN 50155
Vibration and
shock resistance:
Ambient temperature:
Protective coating of the PCB: No
300 V
III
IEC 60664-1
4 kV / 2
AC 2,5 kV; 1 s
AC 4 kV; 1 s
IEC/EN 61326-2-4
IEC/EN 61000-4-2
20 V / m
IEC/EN 61000-4-3
10 V / m
IEC/EN 61000-4-3
2 kV
IEC/EN 61000-4-4
1 kV
IEC/EN 61000-4-5
2 kV
IEC/EN 61000-4-5
20 V
IEC/EN 61000-4-6
Limit value classe B
EN 55011
IP 30
IEC/EN 60529
IP 20
IEC/EN 60529
Thermpolastic with V0 behaviour
according to UL subject 94
Amplitude 0.35 mm,
Frequency 10 ... 55 Hz, IEC/EN 60068-2-6
frequency 2 ... 13.2 Hz, 13.2 ... 100 Hz,
acceleration ± 0.7 gn IEC/EN 60068-2-6
10 gn / 11 ms, 3 pulses IEC/EN 60068-2-27
40 / 070 / 04
IEC/EN 60068-1
EN 50005
DIN 46228-1/-2/-3/-4
0.5 ... 4 mm² (AWG 20 - 10) solid or
0.5 ... 4 mm² (AWG 20 - 10)
stranded wire without ferrules
0.5 ... 2.5 mm² (AWG 20 - 10)
stranded wire with ferrules
6.5 mm
Cross-head screw / M3 box terminals
solid or
2
0,14 ... 0,25 mm
stranded ferruled
2
7 mm
0.5 Nm
DIN rail
IEC/EN 60715
Vertical
(air flow trough ventilation slots
must be ensured)
Approx. 205 g
52.2 x 90 x 71 mm
Category 1, Class B
IEC/EN 61373
OT1, OT2 compliant
Standard Types
RN 5897.12/321
Article number:
• Auxiliary voltage:
RN 5897.12/321
Article number:
• Auxiliary voltage:
• Outputs:
• Setting range pre-warning:
• Setting range alarm:
• With connection facility of a coupling device RL 5898 or RP 5898
• Max. line capacitance:
• Energized or de-energized on trip
• Selection of type of network
• Width:
Ordering Example for variants
RN 5897 .12 /_ _ _ AC/DC 24 ... 60 V 1 kΩ ... 500 kΩ 1 kΩ ... 500 kΩ
7
AC/DC 24 ... 60 V
0069399
AC/DC 24 ... 60 V
AC/DC 100 ... 230 V
0069400
AC/DC 100 ... 230 V
1 changeover contact for pre-warning
1 changeover contact for alarm
1 kΩ ... 500 kΩ
1 kΩ ... 500 kΩ
5 µF
52.5 mm
Setting range Pre-warning
Setting range alarm
Auxiliary voltage
Variant, if required
Contacts
Type
12.07.22 en / 604A