INSTALLER SETUP;
TO ACCESS MENU PRESS ENTER AND SCROLL DOWN TO SYSTEM AND PRESS THE MODE BUTTON.
WARNING PROFESSIONAL ONLY SETTINGS!!
FACTORY DEFAULT?
Restore back to factory defaults.
NO/YES
When selected you will be prompted to select the start month of Standby and the start
month of Heating.
Standby Mode assists in the solar systems off-season maintenance and saves energy as
solar gain may be available but swimming temperature cannot be achieved, or solar
heating is not desired. A 3min flush of the solar collector occurs between the solar start
USE
time and the end time, providing the roof temperature is equal to or greater than the
AUTO STANDBY?
pool, but if that condition does not occur before 1pm (13:00) a solar system flush will
YES/NO
be forced to occur.
A start month of 'always' can be selected which permanently sets the unit into Standby
mode.
Note: In Auto Standby mode the 2nd filter cycle does not run or the Single Filter Cycle is
halved. Auxiliary Heating parameters are kept.
USE SOLAR DRAIN?
If NO is selected then the solar pump will stop if solar heating is no longer required.
NO/YES
If YES is selected the following menu is presented;
PUMP FOR xx MINS
The controller stops all pumps for the selected number of minutes. This allows for the
water to drain out of the solar collectors before the pool pump is restarted. If the pool
DRAIN IS TO STOP
is not at solar limit during the drain process and solar heating becomes available the
PUMP FOR?
system will resume heating.
The system may delay the drain process if the pool is below limit and if the roof
temperature is above the pool temperature.
xx:xx TO xx:xx
ALLOW SOLAR
(RANGES = 06:00-12:00 AND 12:00-21:00)
FROM?
This setting will not allow the solar system to run outside of the times set. (Select 12:00-
12:00 to always allow solar).
You can option to select a 'LIVE' sensor.
USE LIVE SENSOR?
Select YES for a commercial system where the pool sensor is in constant water flow.
NO/YES
If you select NO (recommended) to enable the sampling feature. The controller
assumes that pipe temp is not always pool temp.
Selecting NO will disable the AUX heating function, and Heater Run Times will not be
USE A HEATER?
displayed or selectable under 2. TIMERS.
YES/NO
When YES is Selected, the following menu is presented:
xx:xx (hh:mm)
The pump stops for the selected time period once the temperature limit is achieved
Heating will then remain off until the sample wait period expires.
SAMPLE TIME:
If no sample wait period is active the heating will remain off until the pool temperature
drops ½°C below the temperature limit setting. Due to rounding the actual heating
hysteresis is ±½°C.
GAS HEATER / ELECTRIC HEATER
This setting lets you to select the type of Auxiliary Heater used. Electric heaters/ Heat
HEATER TYPE?
pumps require no cool down.
If GAS HEATER is selected the following will be displayed:
AQUASMART 5 SV v1.4
(RANGE = 03-15 MINUTES)
7