PATENT APPLIED FOR
General Description
The 0160 series curtain fire dampers
are designed to stop the spread of fire
through ductwork, walls and floors in
ventilation systems. When the fusible
link reaches elevated temperature, it
releases interlocking blades closing
the damper by locking into the blade
ramp sealing the damper closed.
With the introduction of Construction
Product Regulation on the 1st July
2013 all fire dampers are required to
meet the product standard BS EN
15650. To achieve this standard the
damper has to be tested to BS EN
1366-2
dynamic
dampers are then classified to BS EN
13501-3
that
clearly
integrity of the damper also in the way
that damper was installed in the
furnace. The standard also now
included testing of fusible link to ISO
10294-4 that comprises of a dynamic
release and holding tests.
The biggest change in the current
Building
regulations
Section 7 and the CPR is fire
dampers have to be CE marked and
that the dampers must be installed as
tested.
The maximum single section unit
tested was 1000mm x 1000mm for
both the HEVAC and AFS frame.
Sizes above the maximum will be
supplied as multi-section and are not
CE labelled due to the current issues
with the extended fields of application
that we will shortly have an answer
on.
Due to continuous product development Advanced Air (U.K.) Ltd
reserves the right to change any information without prior notice.
Burrell Way,
Thetford, Norfolk,
IP24 3QU, England
Tel: +44 (0) 1842 753624
Fax: +44 (0) 1842 762032
fire
test.
The
states
the
Part
B
and
Curtain Fire Dampers
(P
P
)
ATENT
ENDING
Construction Product Regulation
To meet the requirements of the Construction
Products Regulation 1st July 2013 Advanced Air fire
dampers meet the requirements of the Product
Standard BS EN 15650 with a classification under BS
EN 13501-3 as stated in our Declaration Of
Performance that has been assessed by the notified
certification body BRE who have issued a Certificate
of Consistency of Performance No:
P0004.
Installation
Damper/Model
Blockwork
0160-Standard
Wall
Fire Damper
0160-Standard
Drywall
Fire Damper
Blockwork
2550- Motorised
Wall
Fire Dampers
2550- Motorised
Drywall
Fire Dampers
Date
13/01/15
0160 Series
Classification
E120 (ve i<—>o)
E120 (ve i<—>o)
E120 (ve i<—>o) s
E120 (ve i<—>o) s
Spec. No.
Issue
Rev 4
CE –FD Sub
0832-CPR-
Page No.
1