PATENT APPLIED FOR
Product Details
Blades:
Casing:
Springs:
Ramps:
Fusible Link:
Performance:
Further Options:
Note:
New AFS installation for Blockwork and Drywalls -
Fire Damper Testing Details
Test House & Test
Warrington No: 110372
Effectis No: R0345a
0160 HEVAC Frame In Blockwork
Wall
Efectis - No. R0169a, R0169d
0160 HEVAC Frame In Floor
Effectis No: R0320a, R0320b
0160 AFS in Blockwork Wall
Effectis No: R0279a, R0279b
0160 AFS in Plasterboard
Effectis No:R0319a, R0319b
0160 AFS in Plasterboard
Due to continuous product development Advanced Air (U.K.) Ltd
reserves the right to change any information without prior notice.
Burrell Way,
Thetford, Norfolk,
IP24 3QU, England
Tel: +44 (0) 1842 753624
Fax: +44 (0) 1842 762032
Email: [email protected]
Material: 0.8 mm galvanised mild steel
Spigot Length: 50mm
Case length: 180mm
Material: 1.2mm galvanised mild steel.
Constant force springs made from heat treated stainless steel coil.
1.2 mm galvanised mild steel.
1.0 mm Brass soldered for release at 72°C –0/+2. Easy Maintenance Link for easy
testing and reset
Damper suitable for low, medium and high velocity casing (ductwork) leakage.
Spigotted Type – Class C DW144
Easy maintenance link (EML) Release Mechanism Visual Positioner Indicator (VPI)
Micro switches
Size limitations apply to some options, refer to chart
For Blockwork walls we had
to ensure there was no added
cost to the installation. The
unit design allowed the fixing
bracket to be on one side. In
testing the drop rods were
connected
to
a
attached directly to the wall
therefore offering a simple
low cost site installation
Fire Test
BS EN 1366-2
BS EN 1366-2
BS EN 1366-2
BS EN 1366-2
BS EN 1366-2
Curtain Fire Dampers
bracket
Integrity
132 min
132 min
132 min
60 min
132 min
Date
13/01/15
0160 Series
(P
P
ATENT
For drywall installation both
options are available, drop
rods positioned within the
wall & drop rods positioned
outside the wall with the
fixing to the AFS brackets,
which have been successfully
tested to BS EN 1366-2
Classification BS EN 13501-3
E120 (ve i↔o)
E120 (ho i↔o)
E120 (ve i↔o)
E60 (ve i↔o)
E120 (ve i↔o)
Spec. No.
Issue
Rev 4
CE –FD Sub
)
ENDING
Page No.
3