Before you begin

Shipment contents

Check the shipment contains the following items:
Cardax FT Controller 3000
Cardax FT Cabinet

Power supply

The Cardax FT Controller 3000 requires a 13.6 V DC ± 15%. For further detail regarding
power supply refer to the "Technical specifications" section at the end of this installation note.
Plugs PA1, PA2, PA3 and PA4 provide power out connection points via 500mA fuses.
However, this DC voltage out will be approximately 0.5 V DC lower than the voltage supplied
to the Cardax FT Controller 3000. The fuses are resettable, (i.e. under fault conditions, fuses
go high resistance. When the fault subsides or power is removed, then the fuses will cool and
reset themselves).
The current load on these connection points (PA1 to PA4) is in addition to the 1.0A required
by the Cardax FT Controller 3000. When using these connection points, ensure the Power
Supply to the Cardax FT Controller 3000 is capable of supplying the extra current required.
Cabling
For full details on site cabling and recommended cable specifications refer to Chapter 2 of the
Cardax FT Installation manual.
Ethernet cabling
The communications between the CardaxFT Controller 3000 and the Cardax Command
Centre FT Server can either be via a dial up modem or, preferably, via a permanent Ethernet
connection.
For optimum performance 10BaseT unshielded twisted pair (UTP) (CAT5 or better) cable
should be used for Ethernet connections. The Cardax FT Controller 3000 is provided with an
RJ45 socket (P2) for 10BaseT connection.
EMI Cable Shields
To comply with CE requirements and improve noise suppression, an EMI Cable Shield (ferrite
core) should be applied to both the ethernet cable (P2) and the power in cable (P1). There
are two types of shields, (i.e. those that are split and those that are not). The ethernet cable
2
1 x Cardax FT Controller 3000
1 x Cardax FT Controller 3000 Installation Note (this document)
1 x Cardax FT Product Label
1 x Cardax FT Controller 3000 component identification decal
9 x M3 screws
32 x 4k7 ohm resistors
Refer to the enclosed Cardax FT Cabinet Installation Note (part number 3C4513) for
the shipment contents despatched with the Cardax FT Cabinet.
The cabinet for the Cardax FT Controller 3000 has a label on the inside back surface,
indicating it has been configured specifically for this product. The cabinet can be
rotated, however the door must not be re-hinged as the Run LED will not shine through
the door.
Part number 3E1089 R3
March 2003