Anderson FFA10 Посібник з експлуатації - Сторінка 7
Переглянути онлайн або завантажити pdf Посібник з експлуатації для Пальник. Anderson FFA10. Anderson FFA10 13 сторінок.
5. Prepare for startup
Gas line and cooling airline must be equipped with check valves, otherwise flashback may
occur!
1.
Make sure all gas, cooling air ball valves before burner area closed
2.
Confirm that the gas and cooling air have been supplied to the nearest point of burner,
where with manual shut-off valves.
3.
Confirm that the gas and cooling air solenoid valves are properly controlled, that is, the
gas solenoid valve on the firing side is open, the cooling air solenoid valve on the non-
firing side is open, and closed those valves for opposite side.
4.
Adjust the opening of the gas flow needle valve on down comer of each burner, it is
recommended that the opening be 2/3 of the full opening.
6. Burner installation
6.1
Burner bracket installation
Fix the bracket to the steel structure.
6.1.1
1.
Attach the seal plate to burner block, or to the burner bracket, and tighten it with
fixing bolts. Figure 3
2.
The seal plate needs to be cooled by cooling air, it is recommended to use a 2" air
duct, and the pipe towards to the seal plate with an angle, so that the cooling air
can completely cover the seal plate.
Figure 3:FlexFire®Burner standard configuration and seal plate installation
Anderson Thermal Soluions(Suzhou)Co., Ltd
Anderson Thermal Solutions –FFA10 Burner Operation Manual
Warning
Tight to burner
block by bolts
Cooling air for
seal plate
7
Fix to bracket