FoxGate S6200 Series Installation Guide
Chapter 2

Installation Notice

2.1
To ensure the proper operation of FoxGate S6200 series and your physical security,
please read carefully the following installation guide.

Environmental Requirements

2.1.1
The switch must be installed in a clean area. Otherwise, the switch may be damaged
by electrostatic adherence.
Maintain the temperature within 0 to 50 °C and the humidity within 5% to 95%, non-
condensing.
The switch must be put in a dry and cool place. Leave sufficient spacing around the
switch for good air circulation.
The switch must work in the right range of power input (AC power: 100 ~ 240VAC
(50Hz))
The switch must be well grounded in order to avoid ESD damage and physical injury
of people.
The switch should avoid the sunlight perpendicular incidence. Keep the switch away
from heat sources and strong electromagnetic interference sources.
The switch must be mounted to a standard 19'' rack or placed on a clean level
desktop.
2.1.1.1 Dust and Particles
Dust is harmful to the safe operation of FoxGate S6200 series. Dust can lead to
electrostatic adherence, especially likely under low relative humidity, causing poor
contact of metal connectors or contacts. Electrostatic adherence will result in not only
reduced product lifespan, but also increased chance of communication failures. The
recommended value for dust content and particle diameter in the site is shown below:
Max Diameter (µm)
Max Density
(particles/m³)
Table 2-1 Environmental Requirements: Dust content
Hardware Installation
0.5
1
5
1.4×10
7×10
1

Chapter 2 Hardware Installation

3
5
5
2.4×10
5
5
1.3×10