Display mode 1: normal operating mode. When the power is turned on, the
upper display window shows the measured value (PV) and the lower window
shows the four-digit set value (SV).
Display mode 2: checking the step status. Press the DOWN arrow key once
to change the display from mode 1 to mode 2. The upper display window shows
your current reading temp, and the lower window shows the current step
segment number starting at "P". Press DOWN arrow key to go back. Then press
DOWN arrow key again to show the timer information. The upper display window
shows your current reading temp, and lower window shows the time which
current step has run starting at "F". This timer unit depends on parameter SEC
(note 5.3.16.). It can be either by minute (SEC = 0) or by second (SEC = 1).
Press DOWN arrow key again to return to the display mode 1.
Display mode 3: Ramp soak step settings. Press and hold SET key and A/M
keys together for 3 seconds to change the display from mode 1 to mode 3. This
mode is used for step program settings and step control parameters.
Display mode 4: Parameter setting mode. Press and hold the SET key for 3
seconds to enter the display mode 4. The top window shows the name of a
parameter and the bottom window shows its value. Use the UP and DOWN arrow
key the change the value; use the SET key to save the change and go to the
next parameter.
Display mode 5: Step jumping. Press and hold A/M key for 3 seconds and you
will see current reading temp on the top and current step segment number on
bottom. The decimal point on the right bottom display is flashing. Use UP and
DOWN arrow keys to change the step segment number, then press and hold
A/M key for 3 seconds to confirm and jump.
Display mode 6: Change set temp (single step mode only). For single step
mode (RUN = 0), user can change set temperature by pressing and holding UP
arrow keys for 3 seconds. Then use UP and DOWN arrow key to change its
value. Press SET key once to confirm and exit.
5. Parameter Settings
5.1. Parameter setup mode
When the display mode is 1 or 2, press SET and hold for roughly 2 seconds until
the parameter setup menu is displayed (display mode 3). Please refer to 5.3 for
how to set the parameters.
5.2. Setup flow chart
While in the parameter setup mode, use ▲ and ▼ to modify a digit and use A/M
to select the digit that needs to be adjusted. Press the A/M and SET key at the
same time to exit the parameter setup mode; otherwise, the instrument will
automatically exit if no key is pressed for 10 seconds. Figure 4 is the setup flow
chart. Please note that changed parameter will be automatically registered
without pressing the SET key. If the controller is locked (see 7.16), only limited
parameters (or no parameters) can be changed.
2020.06
5.3. List of system parameters
Table 2. System parameters.
System Parameter Menu
Press & Hold SET Key for 3s to Enter
Code
Description
Alarm 1 Setting
AL1
AL2
Alarm 2 Setting
Input offset
Pb
Proportional
P
Constant
Integral Time
I
D
Derivative Time
Cycle Time
t
FILt
Digital Filter
Hy
Hysteresis Band
Decimal Point
dP
Position
OUTH
Output High Limit
OUTL
Output Low Limit
At
Auto Tuning
Configuration
LocK
Privilege
Input Sensor Type
Sn
OP-A
CF
Display Temp Unit
Alarm Output
ALP
Definition
System Function
COOL
Selection
Display High Limit
PuH
Display Low Limit
PuL
Communication
Addr
address
Communication baud
bAud
rate
Set Temp Menu (Single Step Mode Only, RUN = 0)
Press & Hold Up Arrow Key for 3s to Enter
Code
Description
SP
Set Point
Ramp Soak Step Menu
Press & Hold SET and A/M Keys Together for 3s to Enter
Code
Description
SEC
Timer Unit
LOOP
Program Cycling
PDE
Power Outage Mode
SsB
Safety Start Band
RUN
Program Control
PRO
Program Step Jump
R01
Ramp Time 1
T01
Soak Time 1
Set Temp 1
C01
...
Ramp Time 32
R32
Soak Time 32
T32
Set Temp 32
C32
WWW.AUBERINS.COM
Initial
Setting Range
Remarks
Setting
-1999 ~ +9999
200
See 5.3.1
0 ~ 200
10
± 20.0
0
See 5.3.2
0 ~ 5000
0
See 5.3.3
0 ~ 3000
500
0 ~ 2000
100
2 ~ 120
10
See 5.3.4
0 ~ 50
20
See 5.3.5
0.1 ~ 50.0
0.5
See 5.3.6
0 ~ 1
1
See 5.3.7
outL ~ 200%
200%
See 5.3.8
0 ~ outH
0
See 5.3.3,
0 ~ 1
0
section 3)
0 ~ 50
0
See 5.3.9
See 5.3.10
K
Reserved
C, F
C/0
See 5.3.11
0 ~ 10
1
See 5.3.1
0 ~ 1
0
See 5.3.12
PuL ~ 9999
1300
See 5.3.13
-1999 ~ PuH
0
0 ~ 255
1
See 5.3.14
3 for
9600
Initial
Setting Range
Remarks
Setting
PuL ~ PuH
100
See 5.3.15
Initial
Setting Range
Remarks
Setting
0 ~ 1
0 for min.
See 5.3.16
0 ~ 1
1
See 5.3.17
0 ~ 3
2
See 5.3.18
0 ~ 100.0
100
See 5.3.19
0 ~ 3
0
See 5.3.20
0 ~ 64
0
See 5.3.21
0 ~ 2000
0
0 ~ 9999
0
See Section 6