DuctSox U-Track Посібник з монтажу - Сторінка 6
Переглянути онлайн або завантажити pdf Посібник з монтажу для Промислове обладнання DuctSox U-Track. DuctSox U-Track 16 сторінок.
Endcap
A U-track Endcap gives the U-track a nice finished look on cut ends. Endcap
is friction-fit and simply needs to be pressed into place. A sheet metal screw
should be used to hold the endcap in place.
Step 3 - 1 Row Style
Determine placement of track (both track path and elevation). The bottom
of the U-Track must be mounted 1.5" (38mm) for standard Glider and
Cord-In is 0.5" (13mm) above the
12:00 location of the DuctSox.
Track supports are spaced between
5 to 8 ft (1524 to 2440mm) apart
with a maximum of 8 ft (2440mm).
Additional Track Supports must
also be mounted at both ends of
continuous track runs for stabilization
(or as an alternative, the track can
be secured by mounting the ends
with threaded rod). The track support
cable will need to be mounted at
angles away from the sides of the track along with angled cables in-line with the track. See image above.
T's
There should be roughly 12" (305mm) from sidewall of DuctSox to the start of the branch track. Track too
close to the main run may cause premature failure due to abrasion from the track. Support around fabric
fittings may require additional track supports. NOTE: Offset distance of branch U-Track from main trunk is
approximately half of the main trunk diameter plus 12" (305mm).
6
12"
(305mm)
1.5" (38mm)
Standard
or
0.5" (13mm)
for Cord-In
12"
(305mm)
12"
(305mm)
Installation Guide: U-Track