Configuring Smart-Vector Room Controllers
Diagram 4: Smart-Vector Room Controller fascia
4.1
Before Smart-Vent network panel can be used, each room controller must be configured with a network
address, using the binary "bit-switches" on each room controller. A maximum of 20 addresses can be
configured with the switches.
4.2
Carefully remove the room controller fascia, by prising and unclipping it from the bottom.
4.3
The binary switches are located below the controller display, numbered 1 to 8 (See diagram 4). A switch is on
in the "up" position.
4.4
Switch nos. 1-5 are used to set the network address; switch no. 6 is not used; switch nos. 7 and 8 are used to
set the baud rate at 19200
4.5
Set the network address (room or controller number) and the baud rate using the table below
1
2
1
1
ON
2
2
ON
3
4
4
8
5
16
6
32
7
n/a
8
n/a
ON
ON
4.6
When switches are set, replace the room controller cover.
3
4
5
6
7
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Diagram 5: Location of binary "bit" switches
Room / Controller No.
8
9
10
11
12
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Switch Not Used
ON
ON
ON
ON
ON
13
14
15
16
17
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Page 5 of 8
18
19
20
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON