The output voltage/frequency, Auto bypass status, operating mode in No output
mode or Bypass mode, charger current and battery remaining time function in all
mode could be set directly through LCD module.
In bypass or no output mode, pressing the ENTER-Button on the LCD panel for
more than 1 second to enter setting mode. The LCD display is shown in the
following figure.
The string "OPV" that stands for output voltage. "230Vac" indicates the existing
output voltage is 230Vac. if you want to set output voltage, press the
ENTER-Button for more than 1 second, a flickering string "220" would be shown,
if the ENTER-Button is pressed again, the string "220" turn to flickerless, the
output volt is changed to 220V; if the SELECT-Button is pressed for more than 1
second, the next flickering string "230" appear, the order of flickering string is
220 – 230 – 240 – 220 – 230, Press ENTER-Button to confirm the output volt
what you want.
17
To exit the setting mode that requests a pressing once on the ENTER-Button; to
continue setting, press SELECT-Button. If no any pressing on the
SELECT-Button or ENTER-Button lasting for more than 10 seconds, the setting
mode will exit automatically.
The output frequency string "OPF", Bypass status string " bYPA", operating
mode string "MOdE", battery remaining time string "bATT" , Charger current
string"CHG" would be presented circularly. The only one voltage value can be
selected in "220V", "230V", "240V" at any time; The only one frequency value
can be selected in "50Hz", "60Hz" at any time; Bypass status can be selected in
Bypass Disable or Bypass Enable. The UPS would turn to bypass mode in
several seconds if "Bypass Enable" is selected, and turn to no output mode in
several seconds if "Bypass Disable" is selected; Operating mode can be
selected in "UPS"(normal online mode), "ECO"(high efficiency mode),
"CVF"(converter mode), The mode change would be active only after the UPS is
turned on. The battery remaining time function could be selected in "000" or
"001". (Here 000 means battery remaining time function is disabled, then the
battery remaining time could not display on LCD in battery mode. 001 means
battery remaining time function is enabled, then in battery mode or battery test
mode the battery remaining time (in unit Min or Sec) and string "bATT" would
display on LCD in turn every 2s).