7. Typical Trouble Shooting

If the UPS system does not operate correctly, first check the operating
information on the LCD display. Please attempt to solve the problem using the
table below. If the problem still persists, consult your dealer.
Code
Problem
N/A
No indication, no
warning tone even
though system is
connected to mains
power supply.
N/A
No communication
data.
N/A
Emergency supply
period shorter than
nominal value.
FANF
Fan fail.
HIGH
Battery over voltage.
bLOW
Battery low.
Possible cause
Solution
1) No input voltage.
1) Check building wiring
2) Breaker open.
socket outlet and input
cable.
2) Check the breaker.
Communication wire
Check or change the
is not matched.
communication wire.
1) Batteries not fully
1) Charge the batteries
charged.
until the batteries are
fully charge.
2) Batteries defected.
2) Change the batteries
or consult your dealer.
Fan abnormal.
Check if the fan is
running.
Battery is over
Switching to battery
charged.
mode automatically,
and after the battery
voltage is normal and
the mains is normal, the
UPS would switch to
Line mode
automatically again.
Battery voltage is
When audible alarm
low.
sounding every second,
battery is almost empty.
21
bOPN
Battery open.
CHGF
Charger fail.
dCHF
Digital bigger charger
fail.
bUSH
Bus high.
bUSL
Bus low.
bSFT
Bus soft start fail.
bUSS
Bus short.
TEPH
Inverter temperature
high.
ITPH
Inner ambient
temperature high.
INVH
Inverter high.
INVL
Inverter low.
ISFT
Inverter soft start fail.
NTCO
Inverter NTC open.
Battery pack is not
Do the battery test to
connected correctly.
confirm. Check the
battery bank is
connected to the UPS.
Check the battery
breaker is turn on.
The charge is
Notify dealer.
broken.
The charge is
Notify dealer.
broken.
UPS internal fault.
Notify dealer.
UPS internal fault.
Notify dealer.
UPS internal fault.
Notify dealer.
UPS internal fault.
Notify dealer.
Inside temperature of
Check the ventilation of
the UPS is too high.
the UPS, check the
ambient temperature.
The ambient
Check the environment
.
temperature is too
temperature
high.
UPS internal fault.
Notify dealer.
UPS internal fault.
Notify dealer.
UPS internal fault.
Notify dealer.
UPS internal fault..
Notify dealer.
22