Dataforth DSCP62 Посібник з конфігурації

Переглянути онлайн або завантажити pdf Посібник з конфігурації для Конвертер мультимедіа Dataforth DSCP62. Dataforth DSCP62 3 сторінки. Thermocouple-to-dc current/voltage converter with relay output

DSCP62 Configuration Guide
Thermocouple-to-DC Current/Voltage
Converter with Relay Output
Description
Each DSCP62 Thermocouple Converter provides a single channel of thermocouple
input which is amplified, linearized and converted to a high-level current or voltage
output. Thermocouple type, measurement range, filter, output type and range,
and fault indication may be configured by dip-switch. An auxiliary relay output
is provided to generate an alarm or act as a thermostat. Power can be applied
directly to the converter's terminals or through a DIN rail mounted bus connector
accessory, eliminating the need to wire power to each individual converter.
Specifications
Typical at T
=+25°C and +24VDC power
A
Module
Input (selectable)
Thermocouple Type
EN 60584-1
Input Impedance
Accuracy
Cold Junction Error
Thermal Drift
A/D Conversion
Processing
Response Time, 90% Span
(selectable)
CMRR
Isolation
Dip-Switch Configuration
Status Indicators (LED)
Output (selectable)
Current
Current Output Protection
Fault Output
Voltage
Auxiliary Relay Output
Power Supply
Power Consumption
Hot Swapping
Environmental
Operating Temp. Range
Storage Temp. Range
Relative Humidity
IP Protection
Emissions
Immunity
Mechanical Dimensions (w x h x d)
Housing
Connections
Weight
Dataforth Corporation
3331 E. Hemisphere Loop • Tucson, AZ 85706 USA • Toll Free: 800-444-7644 • Tel: 520-741-1404 • Fax: 520-741-0762 • Email: [email protected] • www.dataforth.com
SD1145 02/11 ©2011 Dataforth Corporation, All Rights Reserved ISO9001:2008 Registered QMS
DSCP62
J, K, E, N, S, R, B, T
Measurement range: Depends on
thermocouple type and dip-switch setting
Span: 100°C (min)
10MΩ
±0.1% (max)
1.5°C (max)
<120ppm/°K
14-bit
Floating point 32-bit
<25ms (without filter), <55ms (with filter)
>135dB, referred to power supply side
1500Vrms (1 minute), 3-Way
Sets input and output ranges, sensor type,
filter and faults
Internal fault, configuration error,
connection fault
0 to 20, 4 to 20, 20 to 0 or 20 to 4mA
Load resistance: 500Ω (max)
25mA (max)
102.5% or 105% of full-scale value in
case of over-range
0 to 5, 1 to 5, 0 to 10 or 10 to 0VDC
Load resistance: 2kΩ (min)
Rated 60mA (max) at 24VAC
19.2 to 30VDC
<600mW (24mA at 24VDC)
Yes
–20°C to +65°C
–40°C to +85°C
0 to 90%, Noncondensing
IP20
EN61000-6-4
EN61000-6-2
0.24" x 3.67" x 4.04"
(6.2mm x 93.1mm x 102.5mm)
Terminal housing for mounting on
35mm DIN 46277
Spring cage clamp
1.6 ounces (46g)
Isolated Analog Signal Conditioning Products
Range and precision of the input
Thermocouple
Range
J
–210 to 1200°C
K
–200 to 1372°C
E
–200 to 1000°C
N
–200 to 1300°C
S
–50 to 1768°C
R
–50 to 1768°C
B
250 to 1820°C *
T
–200 to 400°C
* Up to 250°C, the output is considered equivalent to 0°C.
Auxiliary Output
The auxiliary output is designed to drive an indicator, a relay of greater
power, or the input of a supervisory control system. Through this output the
DSCP62 module can generate an alarm or be utilized like a thermostat. The
normal state of the output depends on the configuration for the fault of the
primary output.
Setting the threshold
The regulation of the threshold is performed through a button located under
the front cover of the module and accessible through the hole using a small
screwdriver.
• Press and release the button. The primary output will start to represent
the value of threshold and the red LED will flash slowly.
• If the button is not pressed again within 5 seconds, the system will
return to standard functioning.
• Each time the button is pressed there is an increase or decrease of the
primary output of approximately 0.2%; the direction of the variation
depends on the configuration of the output.
• If the button is not released but continues to be pressed, a continuous
3% increase starts after 2 seconds.
• When the maximum/minimum value of the chosen scale is reached, the
cycle starts again.
• During regulation of the threshold, the auxiliary output follows standard
functioning, opening and closing as previously set.
• After 5 seconds of no button pressing, the set value is memorized and
the module continues with standard functioning.
Dip-switch SW2.7 details
SW2.7
Regulation type
OFF
Furnace *
ON
Refrigerator *
* In case of choice of direct output: 0(4) to 20mA, 0(1) to 5(10)V
Installation rules
This module is designed for assembly on a DIN 46277 rail. Assembly in a
vertical position is recommended to increase the module's ventilation. Be
sure that no raceways or other objects that compromise aeration are posi-
tioned in the vicinity, and do not position the module above equipment that
generates heat. We recommend positioning the module in the lower part of
the control panel or container compartment. We also recommend rail-type
assembly using the Power Bus connector, which eliminates the need to con-
nect the power supply to each module.
Mean error
0.025% + 0.29°C
0.025% + 0.4°C
0.025% + 0.2°C
0.025% + 0.42°C
0.025% + 1.34°C
0.025% + 1.19°C
0.025% + 1.87°C
0.025% + 0.31°C
Fault
Standard state
Upscale
Closed (LED ON)
Downscale
Open (LED OFF)
DSCP
Resolution
0.12°C
0.17°C
0.92°C
0.19°C
0.66°C
0.59°C
0.9°C
0.13°C
Set threshold
Decrease
Increase
1