reasonable protection against harmful
interference when the equipment is operated
in a commercial environment. This
equipment generates, uses, and can radiate
radio frequency energy and, if not installed
and used in accordance with the instruction
manual, may cause harmful interference to
radio communications. Operation of this
equipment in a residential area is likely to
cause harmful interference in which case the
user will be required to correct the
interference at his own expense.
Specifications
24VAC ±10%, 0.3A 50-60Hz, 7.2VA
Power
power consumption (single Class 2
source only, 100VA or less).
LGnet Port with Ethernet
Communications
10base-T (10Mbps). EIA-485 CMnet port,
twisted pair, selectable for 156 kbps, 38.4
kbps, or 9600 bps. One Console Port for
direct connect or modem. One Access
Port for direct network using an APT. One
Keypad/Display Port (Auxiliary Device
Port).
Environmental Operating Range
130°F (-17.8 to 54.4°C); 10 to 90% relative
humidity, non-condensing.
Status Indication
CMnet, Console Port 1 and Ethernet
communications, errors, running, and
power.
1 MB flash, 1 MB RAM.
Memory
Built-in surge and transient
Protection
protection circuitry.
7-year lithium BR2325 battery
Battery
provides a minimum of 10,000 hours of
data retention during power outages.
UL 916 (PAZX), cUL C22.2
Listed By
No.205 - M1983 (PAZX7), FCC Part 15-
Subpart B - Class A.
Revised 12/22/99 • LGE
0 to
Visual (LED) status of
Mounting
Screw the LGE into an enclosed panel using
the mounting holes provided on the cover
plate. Be sure to leave about 2 inches (5
centimeters) on each side for wiring.
Addressing
LGnet Addressing
The LGE has two rotary switches and a DIP
switch used to assign the LGE's LGnet
address. One rotary switch corresponds to the
tens digit and the other corresponds to the
ones digit. DIP switch four corresponds to the
100s digit.
For example, if the LGE's LGnet address is 3,
set DIP switch four to zero (see Figure 2), the
rotary tens switch to zero, and the rotary ones
switch to three (see Figure 3).
NOTE SuperVision v2.6 and some gateways
may not recognize an LGE if its address is
higher than 60. However, LGEs recognize
gateways with addresses from 1 to 199.
Legacy
IP Addr
Figure 2. DIP Switches
10's
Figure 3. Setting the Module's Address
3
© 1999 Automated Logic Corporation
9600/38.4k baud
1
Default/Assigned
2
ARC156/Legacy
3
4
LGnet Address
+0/+100
1's