Automated Logic LGE Технічні інструкції - Сторінка 4

Переглянути онлайн або завантажити pdf Технічні інструкції для Блок управління Automated Logic LGE. Automated Logic LGE 8 сторінок.

Before setting or changing the address, make
sure the LGE's power is off. The LGE only
reads the address when the module is turned
on. After changing the address, you must
transfer memory to the module. Refer to
"Transferring Memory" on page 6.

IP Addressing

TCP/IP must be set up on the workstation
with an active IP address before configuring
the module's IP address (refer to TCP/IP Setup
for SuperVision for a detailed procedure).
You can use a default IP address for the LGE
that is created by the module, or assign an IP
address if required by the customer. The IP
Addr switch (see Figure 2 on page 3)
determines which IP address is used.
• Default: When the IP Addr DIP switch
is set to Default, the following IP
networking parameters are
automatically set on the CEM Parameter
page:
IP Address = 1 92.1 68.1 68.XXX, where
XXX is the LGE's LGnet address (see
"LGnet Addressing" on page 3).
Subnet Mask = 255.255.255.0
Default Gateway Address =
1 92.1 68.1 68.254
NOTE The default gateway address is
an intranet address. This means that
data packets from this address are
dropped by all internet routers and are
not sent beyond the local network
segment.
• Assigned: When the IP Addr DIP
switch is set to Assigned, you must set
the above parameters on the CEM
Parameter page.
Revised 12/22/99 • LGE
Use the following procedure to set the IP
address when using the Default mode:
1. Set the IP Addr DIP switch to Default.
2. Turn the LGE's power on.
3. If using SuperVision v2.6, edit your HOSTS
file to include the following line for each
gateway (see TCP/IP Setup for SuperVision
for a detailed procedure):
192.168.168.x
Where x is the gateway's address as
defined in "LGnet Addressing" on page 3.
4. If using SuperVision v2.6, run Setup.exe
on the disk shipped with your LGE.
This setup copies updated Portman files to
your emsys folder.
5. Configure the connection as Network in
SuperVision Plus v3.01 or NetBIOS in
SuperVision v2.6.
Use the following procedure to set the IP
address when using the Assigned mode:
1. Obtain an IP address from the job site's
Network Administrator.
2. Establish communication with the LGE
through SuperVision using one of the
connection types in Table 1.
Table 1. Connecting with the Workstation
Port
Cable
Ethernet
10baseT
Access Port
APT
Console
DC95, DC99,
Port
or APT
3. Enter the following information, provided
by the Network Administrator, on the CEM
Parameter page:
• the Assigned IP Address
4
© 1999 Automated Logic Corporation
SuperVision
SuperVision
v3.01
v2.6
Network
NetBIOS
Access Port
Direct
Network
Direct
Direct
Connect
Connect