Automated Logic ZN551 Технічні інструкції - Сторінка 4
Переглянути онлайн або завантажити pdf Технічні інструкції для Мережевий маршрутизатор Automated Logic ZN551. Automated Logic ZN551 18 сторінок. Control module
To mount the ZN551
Wiring for power
To wire for power
ZN551 Control Module • Rev. 3/17/2005
measured from its input to ground and must share the same ground as the
control module.
Screw the ZN551 into an enclosed panel using the mounting slots provided
on the cover plate. Leave about 2 in. (5 cm) on each side of the control
module for wiring.
Mounting slot
Mounting slot
CAUTIONS
•
The ZN551 is a Class 2 device (less than 30 Vac, 100 VA). Take
appropriate isolation measures when mounting it in a control panel
where non-Class 2 devices (120 Vac or greater) are present.
•
Do not power pilot relays from the same transformer that powers the
ZN551.
NOTE You can power several control modules from the same transformer if
you maintain the same polarity.
1
Remove power from the 24 Vac transformer.
Pull the screw terminal connector from the control module's power
2
terminals labeled Gnd and 24 Vac.
Connect the transformer wires to the screw terminal connector.
3
4
Apply power to the transformer.
Measure the voltage at the ZN551's power input terminals to verify that
5
the voltage is within the operating range of 21.6–26.4 Vac.
Insert the screw terminal connector into the ZN551's power terminals.
6
7
Verify that the Power LED is on and the Run LED is blinking.
4
© 2005 Automated Logic Corporation