5. BALLAST WIRING BLOCK DIAGRAM
Illustration 3
HOT A.C. LINE
COMMON
TBTS
6. LABELS
Attach the appropriate labels adjacent to the
Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to
service the fixture.
7. COMPLETING INSTALLATION
When the installation is complete, switch the A.C. power on and join the
Normal Mode - A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The
standby charging mode. The
Emergency Mode - The A.C. Power fails. The
Emergency Mode
. One lamp is illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. Power is
FPDL-32
restored, the
switches the system back to the
Instruction Manual.
Pressing the red lens on the
mode. This interrupts power to the emergency lamps only. The emergency lamp is now being lit by the
bright than the other lamps in the system. To simulate a BLACK OUT use the or circuit breaker to turn off A.C. Power.
Initial Testing - Allow the unit to charge approximately 1 hour, then press the
Allow a 24 hour charge before conducting 90 minute test.
FPDL-32
The
is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code,
outlines the following schedule:
Monthly - Insure that the
. One lamp should operate at reduced output.
Annually - Insure that the
intended for the duration of the test.
"Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction."
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Switched Fixture
BLACK
A.C. BALLAST
WHITE
WHT/BLK
WHITE
(277V) ORG
FPDL-32
1
(120V) BLK
WHT
WHT/RED
+ RED
+ RED
1
Select proper voltage lead. Cap unused lead.

OPERATION

TBTS
will be lit providing a visual indication that the battery is being charged.
FPDL-32
TESTING & MAINTENANCE
TBTS
turns off the light on the
TBTS
is illuminated. Conduct a 30 second discharge test by depressing the
TBTS
is illuminated. Conduct a full 1 1 /2 hour discharge test. The unit should operate as
HOT A.C. LINE
COMMON
TBTS
TBTS
. Annotate Re-lamping label for lamp type and wattage. The
senses the A.C. Power failure and automatically switches to the
Normal Mode
and resumes battery charging. See page 1 of the
TBTS
and forces the unit into emergency
Page 3
Unswitched Fixture
BLACK
WHITE
WHT/BLK
WHITE
(277V) ORG
1
(120V) BLK
WHT
WHT/RED
+ RED
+ RED
1
Select proper voltage lead. Cap unused lead.
FPDL-32
unit connector.
FPDL-32
TBTS
to conduct a short discharge test.
TBTS
A.C. BALLAST
FPDL-32
FPDL-32
is in the
unit and will be less