HID VertX EVO V1000 Посібник з монтажу - Сторінка 3

Переглянути онлайн або завантажити pdf Посібник з монтажу для Контролер HID VertX EVO V1000. HID VertX EVO V1000 19 сторінок.

HID VertX EVO V1000 Посібник з монтажу
VertX EVO V1000 Installation Guide

Introduction

HID's VertX EVO open platform is flexible and scalable to permit economic and high performance access control
solutions for a wide range of applications. The VertX EVO V1000 interconnects through different sub-networks and
protocols to a standard TCP/IP network with the capability of a variety of applications.
For example, the VertX EVO Access Controllers are a cost-effective method for two-way communication using Ethernet
between a computer and a V1000. In addition, the VertX EVO V1000 communicates through a RS-232 serial port and
multi-drop RS-485 ports.

Parts List

Description
VertX EVO™ units (one of the following):
V1000 (Access Controller)
Note: Each VertX EVO controller has a plastic base and is covered with a plastic lid.
- Lithium Battery
- Mounting screws
- 2.2K EOL resistors
- Quick Installation Guide
- Installation Wiring Diagram Example
Note: One or more VertX Interface panels are required when installing a VertX EVO V1000 controller.

Product Specifications

Description
Power Supply
Maximum Current at 12-24VDC per Unit
Average Operating Current at 12VDC
Operating Temperature Range
Humidity
SD Card
USB Port

Cable Specifications

Cable Type
RS-485 *
4000 feet (1220 m) to host
Input Circuits *
500 feet (150 m)
Output Circuits *
500 feet (150 m)
500 feet (150 m) to reader
Wiegand
Ethernet
328 feet (100 m)
Power Supply
----
12-24 VDC IN
* Minimum wire gauge depends on cable length and current requirements.
July 2011
Specification
12-24VDC
1 Amp
210mA
32°-120°F (0°- 49°C)
5% to 85% non-condensing
Reserved for Future Use
Reserved for Future Use
Length
Using Belden 3105A, 22AWG twisted pair, shielded 100 cable, or
equivalent.
2-conductor, shielded, using ALPHA 1292C (22AWG) or Alpha 2421C
(18AWG), or equivalent.
2-conductor, using ALPHA 1172C (22AWG) or Alpha 1897C (18AWG),
or equivalent.
ALPHA 1299C, 22AWG, 9-conductor, stranded, overall shield.
Fewer conductors needed if all control lines are not used.
Cat5, Cat5E, and Cat6
Refer to your Power Supply Installation Guide.
© 2003 - 2011 HID Global Corporation. All rights reserved.
Quantity
1 V1000 used with
any combination of
(up to 32) interface
panels.
1
4
8 ea V1000
1
1
Specification
Page 3 of 19