ADEMCO Honeywell 5806 W3 Посібник з усунення несправностей - Сторінка 5
Переглянути онлайн або завантажити pdf Посібник з усунення несправностей для Датчики безпеки ADEMCO Honeywell 5806 W3. ADEMCO Honeywell 5806 W3 9 сторінок. Smoke & heat detector
Smoke & Heat Detector Troubleshooting
Testing the Smoke Detector
To test that your smoke detector is functioning properly:
1. Place your system in Test mode. Please refer to the
2. Locate the Test Switch on the detector housing. This may be a recessed switch or a visible button.
3. Depress the Test Button, if present. For a recessed test switch, use a small screwdriver or Allen key
(no more than 0.18" diameter) to push and hold the recessed test switch for at least 5 seconds. The
smoke detector LED should blink once per second and the smoke detector sounder (not the system
siren) sound within 3 seconds, indicating that the detector is functioning properly. Release the Test
Button or remove the tool from the recessed switch to silence the smoke detector sounder.
4. Remove your system from Test mode. Please refer to the
Heat Detector Trouble Conditions
Heat Detectors do not have LEDs or sounders to indicate trouble conditions. Any trouble
conditions detected will show on your alarm keypad. Note: the actual message will vary
depending on your keypad model. Please refer to the
for details about your keypad model.
https://alpha.adt.com/help/89[11/12/2018 9:58:31 PM]
System Test
System Test
System Panel Troubleshooting
opening above batteries.
page.
page.
page