Centipede 2® Module™ Temperature Control System
Detect and Assign Control Zone IDs
Enumerate Control Zone IDs
'En' Command
Type En and then press [Enter].
Detects all installed zones. All zones get assigned an ID that matches physical location in
sequence in the strings. Numbered in sequential order zones 1,2,3,,....
After performing the 'En' function, perform the 'Sm' command to confirm that the required
zones are detected. See Detect and View Control Zones.
Screenshot:
BH> En
Enumerating Modules
Note: Exiting a session (disconnect) without typing the Bye command the system is hung in
session and cannot login without power cycle.
Detect and View Control Zones
'Sm' Command
Type Sm and then press [Enter].
Displays all zones with a Zone ID. Verify that the required numbers of zones are detected
for your installation.
If there are multiple zones with the same Zone ID or there are missing zones,
perform an IDRESET. See Reset Zone IDs and Settings.
Screenshot:
BH> sm
Enumerated modules
1, 2, 3
Reset Zone IDs and Settings
'Idreset' Command
Type Idreset and then press [Enter].
Resets and auto-assigns all Zone IDs. This function should be performed when there are
multiple zones with the same Zone ID (e.g. 1, 1, 2, 2, 3, 3) or when you wish to reset all
temperature zone register values.
This function resets all temperature zone register values (set-point, high-limit,
etc.) back to its default parameters. See Appendix B for a list of all default
module register values.
Screenshot:
BH> sm
Enumerated modules
®
BriskHeat
Corporation. All rights reserved
7
Centipede 2® Module™ Temperature Control System
1,
1,
2
BH> idreset
Resetting Module/Zone ID(s)
BH> sm
Enumerated modules
1,
2,
3
Manually Set an Individual Zone ID
'Idset' Command
Type Idset:X:Y and then press [Enter].
X = Physical Zone Location
Y = Desired Zone ID #
Set a specific Zone ID number to a single zone.
In the screenshot example below, the user changes the Zone ID of the first zone
to 55.
Screenshot:
BH> idset:1:55
Setting Module/Zone ID
BH> sm
Enumerated modules
55,
2,
3
Manually Set Multiple Zone IDs
'Idsetr' Command
Type Idsetr:X:Y:Z and then press [Enter].
X = Physical Zone Location of the First Zone to Change
Y = Desired Zone ID # of First Zone to Change
Z = Number of Zones to Change
Set multiple zone IDs in sequence at one time.
In the screenshot example below, the user changes the Zone ID of the fourth physical zone
to 10. The user also requires three zone IDs to be assigned starting with the fourth
physical zone. The three zones are re-assigned to the desired sequence: 10, 11, 12.
Screenshot:
BH> idsetr:4:10:3
Setting Module/Zone ID
BH> sm
Enumerated modules
1,
2,
3,
10,
®
BriskHeat
Corporation. All rights reserved
11,
12