Centipede 2® Module™ Temperature Control System

Reload Default Parameters

'Reload' Command
Type Reload and then press [Enter].
Screenshot:
BH> reload
Reloading default parameters

Program Temperature Control Zones

1.
Select the Temperature Zone that you would like to program
a)
Option 1: Program All Temperature Zones:
Command: wr:3,0
a)
Option 2: Program an Individual Zone
Command: wr:3,X (X= zone number)
2.
Select the Temperature Zone Setting that you would like to program
Setting
Command
Set-Point
wr:4,5,X00
1
Temperature
(X= temperature in °C)
High-Limit
wr:4,6,X00
2
Temperature
(X= temperature in °C)
Low-Limit
wr:4,7,X00
3
Temperature
(X= temperature in °C)
Disable /
Disable: wr:4,4,0
4
Enable Zone
Enable: wr:4,4,64
See Appendix B for a complete list of Control Zone Register Definitions.
Screenshot of Global Programming
BH> wr:3,0
Focus on all zones. Press [Enter]
BH> wr:4,5,15000
Set-Point 150°C. Press [Enter]
BH> wr:4,6,17000
High-Temperature Limit 170°C. Press [Enter]
BH> wr:4,7,13000
Low-Temperature Limit 130°C. Press [Enter]
Screenshot of Individual Zone, Example: Zone 2
BH> wr:3,2
Focus on individual zone. Press [Enter]
BH> wr:4,5,14000
Set-Point 140°C. Press [Enter]
BH> wr:4,6,18000
High-Temperature Limit 180°C. Press [Enter]
BH> wr:4,7,12000
Low-Temperature Limit 120°C. Press [Enter]
®
BriskHeat
Corporation. All rights reserved
Example
wr:4,5,15000
Programs set-point to 150.00°C
wr:4,6,17000
Programs high-limit to 170.00°C
wr:4,7,13000
Programs low-limit to 130.00°C
Default setting: Enabled
9
Centipede 2® Module™ Temperature Control System

Read / View Status of Temperature Control Zones

1.
Select the Temperature Zone that you would like to view
a)
Command: wr:3,X (X= zone number)
2.
Select the Temperature Zone Setting that you would like to view
Setting
1
Set-Point Temperature
2
High-Limit Temperature
3
Low-Limit Temperature
4
Zone Config
5
Duty Cycle
See Appendix B for a complete list of Control Zone Register Definitions.
Screenshot Example: Viewing Set-Point of Zone 1
BH> wr:3,1
Focus on zone 1. Press [Enter]
BH> rr:4,5
View Set-Point (register 5). Press [Enter]
150

Dump Command (Data Logging)

Type dump [Enter]
Screenshot of Dump Command (Data Logging)
BH> dump
Data log every 10 seconds
14:04:40 20140102 Z0001 ST8001 S0050.0C H0060.0C L0040.0C PV0021.7C DC100% HTOK
14:04:40 20140102 Z0002 ST8001 S0050.0C H0060.0C L0040.0C PV0023.8C DC100% HTOK
14:04:40 20140102 Z0003 ST8001 S0050.0C H0060.0C L0040.0C PV0025.1C DC100% HTOK
14:04:50 20140102 Z0001 ST8001 S0050.0C H0060.0C L0040.0C PV0022.1C DC100% HTOK
14:04:50 20140102 Z0002 ST8001 S0050.0C H0060.0C L0040.0C PV0024.2C DC100% HTOK
14:04:50 20140102 Z0003 ST8001 S0050.0C H0060.0C L0040.0C PV0025.5C DC100% HTOK
a
b
c
d
e
a)
Time format: hh:mm:ss
b)
Date format: yyyymmdd
c)
Zone number
d)
Status
e)
Set-point
To Exit Dump (Data Logging): Press [Enter] key
®
BriskHeat
Corporation. All rights reserved
Command
rr:4,5
rr:4,6
rr:4,7
rr:4,4
rr:4,12
f
g
h
i
j
f)
High Alarm Limit
g)
Low Alarm Limit
h)
Actual Temperature
i)
Duty Cycle
j)
Heater Status