AB Quality MobileView Guard G750 Посібник із швидкого старту - Сторінка 16
Переглянути онлайн або завантажити pdf Посібник із швидкого старту для Сенсорні термінали AB Quality MobileView Guard G750. AB Quality MobileView Guard G750 20 сторінок.
16
MobileView Guard G750
Power Supply Requirements
Electrical Specifications
24V dc Power Supply
Grounding
ATTENTION
!
Publication 2727-QS002E-MU-P
Use a 24V dc Safety Extra Low Voltage power supply.
Supply Voltage Range: 18V dc to 32V dc
Current Consumption: 300mA at 24V dc
Peak Inrush Current: 5.6 A maximum
Connect Earth Ground to the Junction Box using the Earth
Ground Screw (shown on page 14).
• The device meets the safety class III in accordance with EN
61131-2 and EN 50178. The 24V power supply for the
equipment must provide appropriate isolation between the
safety-extra-low-voltage circuits and dangerous-contact
voltage circuits (for example, by safety transformers or
similar facilities).
• The power supply circuit must be protected with a 3.15 A
fuse.
• The nominal supply voltage directly of the MobileView
terminal (without the MobileView Connection Cable) is
+24V dc (supply voltage range: 18 to 32V dc).
Typical current consumption is:
- 300 mA at 24V dc
-400 mA at 18V dc
When planning the power supply, take into account the
voltage drop on the Connection Cable.
Specification of power supply lines in this cable:
Cross section: AWG24 (0.24 mm
Material: zinc-coated copper strand
Line resistance:
2
)
<
<
90 Ohm/km (
145 Ohm/mile)