Electrical (continued)
115V WITH 12 GAUGE POWER CORD
1 - Remove long hex adapter (part A) off pump
2 - Remove pump box cover (four screws included with pump
3 - Unscrew and realign the brass bridge (part H), and brass washers (part I), to match 115V wiring diagram (see figure 5)
4 - Run the 12 gauge cord through black rubber o-ring (part F). Insert cone gasket into the black hex cap (part B).
5 - Pull wires into pump box, per wiring diagram
6 - install black cord strain relief (part D)
7 - Use included screws (part G), to secure black cord strain relief (part D)
8 - Tighten black hex cap (part B) to pump box
9 - Reinstall box cover
WIRING
Pump must be permanently connected to circuit. Table I gives correct wire and circuit breaker sizes for the pump alone. It is recommended
to use a dedicated breaker; however If other lights or appliances are also on the same circuit, be sure to add their amp loads to pump amp
load before figuring wire and circuit breaker sizes. (If unsure how to do this or if this is confusing, consult a licensed electrician.) Use the
load circuit breaker as the master on-off switch.
Install a Ground Fault Circuit Interrupter (GFCI) in circuit; it will sense a short-circuit to ground and disconnect power before it becomes
dangerous to pool users. For size of GFCI required and test procedures, see GFCI manufacturer's instruction.
In case of power outage, check GFCI for tripping (which will prevent normal pump operation). Reset if necessary.
NOTE: If you do not use conduit when wiring motor, be sure to seal wire opening on end of motor to prevent dirt, bugs, etc. from entering..
Motor HP
Branch Fuse Rating Amps*
1
20
1-1/2
1
15
1-1/2
* Time delay fuses are recommended instead of standard fuses in any motor circuit
** Chart is for reference only. Refer to National Electic Code for details
*** Copper conductor only
**** If 208V, please call factory

Operation

Max Load Amps
Voltage/Hz/Phase
7.5
115/60/1
14
3.5
230/60/1
7.0 - 7.2
Figure 10 - Wire Gauge Matrix For APEX Series Pumps
10
Service to Motor - Distance in Ft . (m)
0-100'(0-30)
101-200'(30-60)
AWG Wire Size (mm²)
10(5.5)
12(3)
8(8.4)
14(2)
201-300'(60-90)
8(8.4)
6(14)