Aquatech Pressmain MG-LT Інструкція з експлуатації - Сторінка 17

Переглянути онлайн або завантажити pdf Інструкція з експлуатації для Блок управління Aquatech Pressmain MG-LT. Aquatech Pressmain MG-LT 20 сторінок. Tankmatic tank level/temperature monitoring/control unit with smart relay control

Aquatech Pressmain MG-LT Інструкція з експлуатації
2.4 
ALARMS 
 
Display giving type of fault and volt‐free output signal (where fitted) 
and audible alarm (where fitted).  
Automatic reset of alarms is provided 
Note: fault messages are scrolled through automatically. 
If more than 1 fault message is activated then all messages will be 
scrolled through. 
 
Please note: The alarm screens shown on the unit are dependent on the  
unit type, i.e. 1 or 2 tanks, Level and/or Temperature etc. 
 
 
 
** System Alarm Message ** 
LOW WATER LEVEL/LOW LEVEL 
APPROACH 
HIGH WATER LEVEL/HIGH LEVEL 
APPROACH 
LOW WATER TEMPERATURE 
HIGH WATER TEMPERATURE 
RELAY OUTPUT DISABLED 
NO WATER IN BREAKTANK 
PLEASE NOTE: BUZZER MUTED 
SERVICE DUE TEL: AQUATECH‐
PRESSMAIN 
 
If a problem persists, contact AQUATECH‐PRESSMAIN service department quoting the serial 
number WN:_______ (on control panel fascia) 
 
 
Aquatech‐Pressmain Instruction manual\Tankmatic smart relay MG‐LT 
Cause 
Tank level at/below low water 
level/low level approach setting 
Tank level at/above high water 
level/high level approach setting  
Tank water temperature at/below 
low water temperature level 
Tank water temperature at/above 
high water temperature level 
Enable/Disable relay outputs switch 
set to "Disable" 
Where supplied the Low level float 
switch in tank has activated. 
Where fitted, the mute audible 
alarm button has been pressed. 
12 month service timer elapsed 
 
Tankmatic Smart Relay 
SYSTEM ALARM
Info Follows 
30cm 
>
0C
LOW WATER 
TEMPERATURE 
30cm 
>
0C
Check 
Float valve sticking closed. 
Incoming water supply interrupted 
or insufficient to keep up with 
outgoing demand. 
Float valve sticking open. Outgoing 
supply flow reversed back into 
tank. 
Ambient temperature too low. 
Insufficient frost protection. 
Ambient temperature too high. 
Tank heaters set too high. Constant 
running pump causing increase in 
water temperature circulating back 
into tank. 
Usually set to disable relay outputs 
during tank cleaning to prevent 
false alarms on BMS. 
Float valve sticking closed. 
Incoming water supply interrupted 
or insufficient to keep up with 
outgoing demand. 
Automatically resets when alarm is 
no longer present. 
Phone Aquatech‐Pressmain to 
arrange annual service visit. 
 
 
17