4.3 Analogue function
OUT2 is an analogue output:
› [ou2] defines whether the set measuring range is provided as 4...20 mA ([ou2]= [I]) or as 0 ... 10 V ([ou2] = [U]).
› Analogue start point [ASP2] determines at which measured value the output signal is 4 mA or 0 V.
› Analogue end point [AEP2] determines at which measured value the output signal is 20 mA or 10 V.
› Minimum distance between [ASP2] and [AEP2] = 20 % of the measuring span.
Voltage output 0 ... 10 V:
Factory setting
P =
System pressure
MEW = Final value of the measuring range
ASP =
Analogue start point [ASP2]
AEP=
Analogue end point [AEP2]
In the measuring range of the respective unit the output signal is
between 0 and 10 V.
It is also indicated:
› System pressure above [AEP2]: 10 ... 10.3 V
› Fault indication according to Namur: 11 V
4.4 IO-Link
General information
This unit has an IO-Link communication interface which requires an IO-Linkcapable module (IO-Link master) for operation.
The IO-Link interface enables direct access to the process and diagnostic data and provides the possibility to set the parameters of the unit during
operation.
In addition communication is possible via a point-to-point connection with a USB adapter cable.
Further information about IO-Link at www.argo-hytos.com → „Products" → „Pressure Switches" → „TSE3-D".
Device-specific information
You can find the IODDs necessary for the configuration of the IO-Link unit and detailed information about process data structure, diagnostic
information and parameter addresses at www.argo-hytos.com → „Products" → „Pressure Switches" → „TSE3-D".
5 Installation
Before installing and removing the unit: make sure that no pressure is applied to the system.
► Insert the unit in a G¼ process connection.
► Tighten firmly. Recommended tightening torque:
Pressure range in bar
-1 ... 400
Depends on lubrication, seal and pressure load!
The sensor housing can be rotated by 345° with regard to the process connection.
Do not rotate past the end stop!
Page 3
Measuring range scaled
Tightening torque in Nm
25 ... 35
Current output 4 ... 20 mA:
Factory setting
P =
System pressure
MEW = Final value of the measuring range
ASP =
Analogue start point [ASP2]
AEP=
Analogue end point [AEP2]
In the measuring range, the output signal is between 4 and 20 mA.
It is also indicated:
› System pressure above [AEP2]: 20 ... 20.5 mA
› System pressure below [ASP2]: 4 ... 3.8 mA
› Fault indication according to Namur: 21.5 mA.
Subject to change · TSE3-D_9193_1en_09/2019