finder 19.6K Посібник - Сторінка 8

Переглянути онлайн або завантажити pdf Посібник для Контролер finder 19.6K. finder 19.6K 17 сторінок. Knx actuator

finder 19.6K Посібник
1.5.2

DPT_Channel X Force Out (1.001 Switch)

The DPT_Channel X
level, as shown in the table below, regardless of the selected Channel function and the previous output status.
The channel status is set on the value defined by the PAR_Value Force Out parameter if the device receives
the message with value On and is maintained until the DPT_Channel X
with the value Off or a higher priority message is sent to the device. In the forcing state the reception of
messages different from DPT_Channel ALL
by the device and will not have any effect on Changing Channel status. These messages will then be sent back
when the forcing ceases by receiving the DPT_Channel X
Status and DPT_Channel X - Status Inverted messages, activating the forcing status, will always be sent by
the device if they are used in group addresses. By receiving the DPT_Channel X
the channel status remains the one acquired on forcing, until the device gets a message that make it Switch,
except for the case where the channel function is "Stairs lights" that, if lights were lit by forcing, they will turn
off after the period set with the PAR_Stairs Light Time (s) parameter.
1.5.3

DPT_Channel ALL Force ALL Out (1.001 Switch)

The DPT_Channel ALL
outputs have to be forced with the highest priority in the status defined by the PAR_Value Force ALL Out
parameter. In the forcing status the reception of messages different from DPT_Channel ALL
will be ignored by the device and will not have any effect on changing the Channel status. These messages
will then be sent back when the forcing ceases by receiving the DPT_Channel ALL
message. In order to avoid bus overloading by sending datagrams after the activation of the forcing status,
pairs of DPT_Channel X - Status and DPT_Channel X - Status Inverted messages will be sent every 100ms,
starting from Channel 1. The status messages are always sent at the activation of the high priority forcing
independently by of the status of the channels, if any used in the group addresses.
By receiving the DPT_Channel ALL
one acquired on forcing, until the device gets a message that make it Switch, except for the case where the
channel function is "Stairs lights" that, if lights were lit by forcing, they will turn off after the period set with the
PAR_Stairs Light Time (s) parameter.
FINDER SpA
Force Out message allows to control the channel X status with the medium priority
Force ALL Out or DPT_Channel X
Received message
DPT_Channel ALL Force ALL Out
DPT_Channel X Force Out
DPT_Channel X Select Scene
Force ALL Out message is sent to the device, with the value On, each time all
Force ALL Out = Off message, the status of each channel remains the
Ver. 2018
Force Out message will be received
Force Out = Off message. The DPT_Channel X -
Priority
High
Medium
Low
Table 1
KNX Actuator 19.6K
Force Out will be ignored
Force Out = Off message,
Force ALL Out
Force ALL Out = Off
8