finder 19.6K Посібник - Сторінка 9

Переглянути онлайн або завантажити pdf Посібник для Контролер finder 19.6K. finder 19.6K 17 сторінок. Knx actuator

finder 19.6K Посібник
1.5.4

DPT_Channel X Select Scene (18.001 DPT_Scene Control)

Typically, the scenarios are used to set a predetermined channels configuration of the device, when the
function (direct, logical or analog
The DPT_Channel X
scenario for the Channel X. The DPT assigned to this message is 18.001.
User can set up to four different scenarios for each individual channel. If the channel scenarios are enabled
through the PAR_Enable Scenes parameter, the scenarios configuration page appears, on which will include
the relevant parameters. The number that can be set as scenario
parameter
scenario has no effect because even if it was enabled, it is not assigned any numbers. In this way the user has
the option to configure only the scenarios that actually will use. Channel status on scenario Y will be set by the
PAR_Scene Y Value parameter value
can be changed by sending the message DPT_Channel X - Out. If the PAR_Enable Storage for Scene Y
parameter
current status value. When the device receives the message with the value
the PAR_Scene Y Value parameter will update with the current status of the channel set by the user and to
store it for the next recall of scenario Y.
1.5.5

DPT_Channel X - Status e DPT_Channel X - Status Inverted (1.001 Switch)

The DPT_Channel X - Status and DPT_Channel X - Status Inverted messages are relayed from the device on
the bus every time Channel X status switches, as shown in the previous figures.
1.5.6

DPT_Channel X - Logic Input 1 e DPT_Channel X - Logic Input 2 (1.002 Boolean)

If the PAR_Enable Logic Function
the DPT_Channel X - Logic Input 1 and DPT_Channel X - Logic Input 2 messages appear on device
descriptor only if the PAR_Logic Operator parameter is set to AND, OR, XOR. They are the Boolean values to
be sent to the device and that will be composed with the DPT_Channel X Set ON/OFF message for channel
switching.
1.5.7

DPT_Channel X Lock PORT (1.002 Boolean)

If the PAR_Enable Logic Function
appear on device descriptor, together with the PAR_Value PORT Locked parameter, which defines the value
that the message must have to lock the logic function PORT formed with the input channel switching.
The DPT_Channel X
accordance with the selected function, only if device has not received previously the DPT_Channel X
PORT message with the value set by the PAR_Value PORT Locked parameter. Otherwise the channel status
preserves the value it had before the switching request, meaning that all DPT_Channel X
messages received after locking the PORT will not be considered by the device.
1.5.8

DPT_Channel X - High Threshold and DPT_Channel X - Low Threshold (7.001Value_2_Ucount)

These messages allow to change run-time the thresholds set by the PAR_Upper Threshold and PAR_Lower
Threshold parameters without overwriting them. They only appear on the device descriptor if the
PAR_Enable Logic Function
Operator
FINDER SpA
Set
Select Scene message is sent to device whenever user wants to recall an expected
-64]. Leaving the parameter with the default value No scene number , the
, the user is able to reprogram the channel status of the scenario with the
DPT_Channel X Select Scene = 0x80 | PAR_Scene Y Number
Set ON/OFF message will have effect in order to change the channel status in
Ver. 2018
PAR_Function parameter is set to value 0.
is attributed to the PAR_Scene Y Number
and the PAR_Logic Operator
DPT_Channel X
KNX Actuator 19.6K
channel output status
Lock PORT message
Lock
Set ON/OFF
chosen by the PAR_Logic
9