When using the FlexProbe
important to select the range that provides the
best resolution. Failure to do this may result in
measurement errors.
•
For best results, select the highest FlexProbe
output signal possible and the most sensitive
meter range for this output.
•
Make sure the DMM or measuring instrument can
accurately measure mV
DMM have poor resolution and accuracy when
measuring low mV
.
AC
•
For best accuracy, center the FlexProbe
the conductor to be measured.
•
To increase the sensitivity or measure on low cur-
rents, the FlexProbe
®
times around the conductor. Remember to divide
your reading by the number of turns for the actual
measurement (See Figure 1).
•
The overall measurement accuracy is the sum of
the FlexProbe
accuracy and the displaying instru-
®
ment accuracy.
•
The FlexProbe
may be doubled around the con-
®
ductor to be measured to double the output. (See
DMM while measuring 250A