Ariston microGENUS 23 MFFI Інструкція з монтажу Посібник з монтажу - Сторінка 12
Переглянути онлайн або завантажити pdf Інструкція з монтажу Посібник з монтажу для Котел Ariston microGENUS 23 MFFI. Ariston microGENUS 23 MFFI 25 сторінок. Type c boilers
Також для Ariston microGENUS 23 MFFI: Посібник користувача (24 сторінок), Інструкція з обслуговування (28 сторінок), Інструкція з обслуговування (28 сторінок)
T
P
WIN
IPE
S
YSTEMS
F
. 2.11
IG
2.10 R
T
OOM
HERMOSTAT
C
ONNECTION
To connect a room thermostat, it is necessary to:
1. - Open the control panel as indicated in section 3.3.
2.- Remove the link "A" from the terminal block on the reverse of the control panel.
3. - Insert the thermostat cable through the cable grommet and fasten it by means of the
cable-clamp provided.
4. - Then connect the thermostat wires to the terminal block.
5.- If a remote time clock is to be fitted, disconnect the integral time clock from the P.C.B.
6. - Using a volt-free switching time clock, connect the switching wires from the time clock
following points 1-4 above.
7. - If using an external time clock and room thermostat, these must be connected in
series as points 1-7 above.
Note: Only a two-wire type room thermostat can be used.
An anti-frost device is built-in to the appliance's electronic regulation
system.
A
In calculating the lengths of the pipes, the
maximum length "L" must also take into
consideration
exhaust/air intake end terminals, as well
as 90° elbows for coaxial systems.
The C52 types must comply with the
following requirements:
1 - The exhaust/ air intake pipes must
have the same diameter of
2 - If elbows are to be inserted into the
air intake and/or exhaust system, the
calculation of the overall length must
take into consideration the values for
each elbow, see the F
A
3 - The exhaust pipe must protrude by at
least 0.5 m above the top of the roof
in the event that it is located on the
opposite side to the side with the air
intake (this condition is not obligatory
when the air intake and exhaust are
located on the same side of the
building).
FU007A
Fo016A
12
the
values
M
.
CCESSORIES
ANUAL
for
the
80 mm.
ø
P
L U E
I P E
Fo017A