Installation instructions
Important - safety
requirements
Where applicable Natural Gas and L.P Gas
versions of this appliance are available.
Check that this model is suitable for the type
of supply available. This appliance must be
installed and/or serviced by a competent
person in accordance with the Gas Safety
(Installation and Use) Regulations Current
Editions and the I.E.E. Wiring Regulations.
Detailed recommendations are contained in
the following British Standard Codes of
Practice – BS.6172, BS.5440: Part 2 and
B.S.6891. All British Standards must be
'Current Editions'.
This
appliance
installed
electrician / competent person
(CORGI Registered). Safety may
be impaired if installation is not
carried out in accordance with
these instructions.
Before connecting the appliance
make sure that the voltage of
your electricity supply is the
same as that indicated on the
rating plate. This is situated on
the lower front frame of the
appliance and can be seen upon
opening the door. Alternatively
the rating plate may also be
found on the back or top of
some
applicable).
Do not alter the electrical
circuitry of this appliance.
34
must
be
by
a qualified
models
(where
Provision for ventilation
This appliance is not connected to a
combustion products evacuation device. It
shall be installed and connected in
accordance with the current installation
regulations. Particular attention shall be
given to the relevant requirements regarding
ventilation.
The room containing the appliance should
have an air supply in accordance with
BS.5440: Part 2 Current Edition. All rooms
require an openable window or equivalent
and some rooms will require a permanent
vent as well. For room volumes up to 5m
air vent of 100cm
2
volumes between 5m
of 50cm
is required. If the room has a door
2
that opens directly to the outside, no air vent
is required. For room volumes that exceed
11m
no air vent is required. If there are
3
other fuel burning appliances in the same
room, BS.5440: Part 2 Current Edition
should be consulted to determine the
requisite air vent requirements.
Prolonged intensive use of the appliance
may call for additional ventilation, for
example opening a window, or more
effective ventilation, for example increasing
the level of mechanical ventilation where
present.
Moving your appliance
You may damage some soft or badly fitted
floor coverings when you move the
appliance.
The floor covering under the
appliance should be securely fixed so it does
not ruck up when you move the appliance
across it. Alternatively you could remove the
floor covering. This appliance is heavy and
care must be taken when moving it. Do not
try to move the appliance by pulling the door
handles.
3
is required: for room
and 10m
an air vent
3
3
an